09.91 11 Alarms
11.11 Alarm list ACKNOWLEDGE
Cause:
Effect:
Remedy:
6128
Wrong I/O jumpering
Same address for central and distributed I/O device
PLC STOP
Change address decoding
Cause:
Effect:
Remedy:
6130
Synch. error basic program
Synchronization pattern for assembler function blocks no longer correct
PLC STOP
PLC OVERALL RESET, reload PLC program if necessary
Cause:
Effect:
Remedy:
6131
Synch. error MC 5 program
Synchronization pattern for STEP 5 program blocks no longer correct
PLC STOP
PLC OVERALL RESET, reload PLC program
6132
Synch. error MC 5 data
Cause:
Effect:
Remedy:
Synchronization pattern for STEP 5 data blocks no longer
correct
PLC STOP
PLC OVERALL RESET, reload PLC program
6133
Illegal block basic program
Effect:
Remedy:
PLC STOP
Replace system software