T
ECHNICAL
N
OTE TNOI34
Title: Communication with Siemens S7-300 PLCs via Ethernet
Product(s): G3, MC, and DSP
ABSTRACT
Crimson 2.0 provides advanced Ethernet communication capabilities for Red Lion Products, G3 HMI,
Modular Controller and Data Station Plus. The Siemens S7-300 Ethernet driver allows users to exchange PLC
data with Red Lion devices using industrial Ethernet networks.
INTRODUCTION
The following technical note presents how to set up the communication between a G3 HMI and an S7-300
PLC using Ethernet and Siemens ISO Protocol. This document can also be used as a reference to set up the
Modular Controller Master and Data Station Plus SX or GT due to similar configuration.
Three major types of connections are available as described below. They will all be presented in this
document. Your application should follow only one of these setups.
Communication with S7-300 CPU with built in Ethernet port and supporting Siemens ISO protocol.
Communication via optional Ethernet card for S7-300 series type CP343-1 supporting TSAP
connections (e.g. CP343-1 Advanced IT).
Communication via optional Ethernet card for S7-300 series type CP343-1 that does NOT support
TSAP connection (e.g. CP343-1 Lean).
The Ethernet driver has been tested and validated with the following products:
CPU315-DP/PN – P# 6ES7 315-2EG10-0AB0, v2.3
CP343-1 – P# 6GK7 343-1EX20-0XE0, v1.1
CP343-1 Advanced IT – P# 6GK7 343-1GX21-0XE0, v1.0
CP343-1 Lean – P# 6GK7 343-1CX00-0XE0, v1.0
NOTE: These features only work with Crimson 2.0 build 315 or above and is only available to Windows 2000
or above users. Please update your version of Crimson 2.0 to the latest available online on www.redlion.net
Zobrazit stránku 0
1 2 3 4 5 6 ... 17 18

Shrnutí obsahu

Strany 1 - OTE TNOI34

TECHNICAL NOTE TNOI34 Title: Communication with Siemens S7-300 PLCs via Ethernet Product(s): G3, MC, and DSP ABSTRACT Crimson 2.0 prov

Strany 2 - Figure 2

Figure 15 Then, click on Address details. This popup window is important as it contains communication information to setup the G306 in Crimson 2 (Fig

Strany 3 - Figure 4

Setting up the G3 for CP343 communication using TSAP connections Once the PLC is setup, all required information is available to configure the G3. Sta

Strany 4 - Figure 5

Figure 18 In this example, the device will be renamed S7300. The device settings have to be set up to fit the PLC configuration (Figure 19). 1. Sele

Strany 5 - Figure 6

Figure 19 Figure 20 Note on Data Type Byte as Byte means the variable will contain a Byte, Byte as Word an integer word and Byte as Long an integer

Strany 6 - Figure 8

SETUP 3 – COMMUNICATION VIA CP343 OPTIONAL ETHERNET CARD NOT SUPPORTING TSAP CONNECTIONS (TRANSPARENT MODE) The following setup is required if you ar

Strany 7 - TSAP CONNECTIONS

When you drop the object on a slot, a window will pop up for the Ethernet configuration. Do as follows (Figure 23): 1. Setup the IP address for the P

Strany 8 - Figure 12

Setting up the G3 for CP343 communication NOT supporting TSAP connections Once the PLC is setup, all required information is available to configure th

Strany 9 - Figure 14

Figure 26 In this example, the device will be renamed S7300. Right-clicking the PLC and selecting “Rename” can achieve renaming. The device settings

Strany 10 - Figure 16

Figure 27 Figure 28 Note on Data Type Byte as Byte means the variable will contain a Byte, Byte as Word an integer word and Byte as Long an integer

Strany 11 - Figure 17

SETUP 1 – S7-300 CPU WITH BUILT IN ETHERNET PORT Setting up the PLC for CPU communication In order to establish the communication, the PLC has to be s

Strany 12 - Figure 18

In the General tab, click on Properties; this opens a popup window where you can set up the Ethernet network. Do as follows (Figure 3): 1. Setup the

Strany 13 - Figure 20

Setting up the G3 for CPU communication Once the PLC is setup, all required information is available to configure the G3. Start Crimson 2.0 software a

Strany 14 - Figure 21

Figure 6 In this example, the device will be renamed S7300. Right-clicking the PLC and selecting “Rename” can achieve renaming. The device settings h

Strany 15 - Figure 24

Figure 7 Figure 8 Note on Data Type Byte as Byte means the variable will contain a Byte, Byte as Word an integer word and Byte as Long an integer l

Strany 16 - Figure 25

SETUP 2 – COMMUNICATION VIA CP343 OPTIONAL ETHERNET CARD SUPPORTING TSAP CONNECTIONS Setting up the PLC for Cp343 communication In order to establish

Strany 17 - Figure 26

When you drop the object on a slot, a window will pop up for the Ethernet configuration. Do as follows (Figure 11): 1. Setup the IP address for the

Strany 18 - Figure 28

Figure 13 Once in NetPro, select the CPU and double click on the first line in the table below. This will open a window to insert a new connection (F