SSA/P Series Electronic Valve Actuator Technical Instructions
24 Vac Floating or 0 to 10 Vdc Control Document Number 155-710
September 16, 2009
Siemens Industry, Inc. Page 3
Service Kits,
Continued
Figure 3.
Block Cover and Terminal Plug
ASY100: Terminal block cover and terminal
plug for SSA/P61U, quantity one
each.
Figure 4. Cable Connector.
ASY8L15: Cable connector, 1.5m cable,
rated, quantity one.
ASY8L45: Cable connector, 4.5m cable,
rated, quantity one.
NOTE: These cables are not plenum rated.
ASY98: Replacement screw and nut for conduit connector quantity one (1).
Operation
The actuators can be driven manually to any position between 0 and 1 with a 3 mm hex
wrench. The control signal from the controller; however, will take priority over any
manual position.
Mounting and
Installation
Figure 5. Mounting Position.
Mount the actuator in one of the allowable positions shown in Figure 5.
NOTE: Vertical is the recommended position.
When mounting the actuator in a plenum, the proper cable must be attached to meet
local codes.
Allow 8-inches (200 mm) above the actuator and 8-inches (200 mm) behind the cable
for service.
Installation Instructions are included with the actuator.