Configuration Examples
6-10
SIMATIC 505 PROFIBUS-FMS CP User Manual
Example of an FMS Read Job (continued)
After
you configure the FMS Read job for Station 1, you need to create a
configuration file for Station 2 by following these steps:
1.
Select the menu command
File →
New
to create an empty
configuration file.
2.
Enter a description for this file in the Description field, as shown below:
Description: File_AB
Next, you must define the Module Local Configuration of the FMS CP
module at Station 2.
1.
Click on the Module Local Configuration icon.
2.
Complete the fields listed below to define the Module Local
Configuration for Station 2.
Local Station Address: 2
Highest Station Address: 15
Bus Parameter Profile: FMS-DP Universal
Baud Rate: 1.5 MBaud
# of Masters (holds token): 6
# of Slaves (no token): 0
Continue
configuring the FMS Read job by defining the FMS connection for
the FMS CP module at Station 2.
1.
Click on the FMS Connections icon of the configuration tree.
2.
Click on the New Item button on the toolbar
.
3.
Complete the fields listed below to define the FMS connection for
Station 2:
Name: Pump
Local LSAP: 5
Remote Station Address: 1
Remote LSAP: 3
Leave
the remaining fields at their default values.
Cr
eating the
Configuration File
for Station 2
Setting the Module
Local
Configuration for
Station 2
Defining an FMS
Connection for
Station 2