3.11 Grounding and lightning protection
25
3.11 Grounding and lightning protection
Building lightning strike protection is described in IEC 62305-3 (EN 62305-3). Among other things, this
standard establishes the classification of individual lightning strike protection systems and indicates the
resulting lightning strike protection measures required.
Grounding and lightning strike protection are to be set up in conformance with IEC62305.
3.11.1 Grounding concept
The design and dimensioning of the grounding system are the main criteria for channeling the lightning
current into the ground (high-frequency behavior) and to reduce dangerous peak currents.
In accordance with DIN EN 62305-3 a low grounding resistance (under 10 , measured at a low
frequency) is recommended.
To avoid high potential differences between the various grounding systems, these are all connected to
the same grounding system.
This is done by connecting the electrical operating areas and the PV field grounding systems to a
comprehensive meshed grounding system.
By meshing all grounding systems, potential differences between the various plant parts are greatly
reduced. In addition, lightning-induced voltage loads on the electrical interconnections between the
buildings are also reduced.
Mesh sizes of 20 m x 20 m up to 40 m x 40 m have proved economically and technically useful in larger
PV systems.