Note
Protect the transmitter from:
Direct heat
Rapid temperature changes
Severe soiling
Mechanical damage
Direct sunlight
Note
Select
the height of the mounting flange such that the pressure transmitter is always mounted
below the lowest fill height to be measured.
The installation location is to be as follows:
Easily accessible
The measuring point must be as close as possible
Vibration-free
Within the permitted ambient temperature values
4.4.2 Installation for level
Note
Seals are required for the installation. The seals must be compatible with the medium to be
measured.
Seals are not included in the delivery.
Procedure
To install the transmitter for level, proceed as follows:
1.
Attach the seal to the container's mating flange.
Ensure that the seal is centrically positioned and that it does not restrict the movement of
the flange's seal diaphragm in any way as otherwise the tightness of the process connection
is not guaranteed.
2. Screw on the transmitter's flange.
3. Observe the installation position.
Installing/mounting
4.4 "Level" installation
SITRANS P, DS III series with HART
44 Operating Instructions, 09/2012, A5E00047092-08