Glossary
DP Base Programming Interface for CP 5613/CP 5614
C79000-G8976-C108-01
233
Maximum station delay
The maximum station delay (max. TSDR) specifies the longest interval required by
a node in the subnet between receiving the last bit of an unacknowledged frame
and sending the first bit of the next frame. After sending an unacknowledged
frame, a sender must wait for the max. TSDR to elapse before sending a further
frame.
Minimum station delay
The minimum station delay (min. TSDR) specifies the minimum time that the
receiver of a frame must wait before sending the acknowledgment or sending a
new frame. The min. TSDR takes into account the longest interval required by a
station in the subnet for receiving an acknowledgment after sending a frame.
min T
SDR
see "Minimum station delay"
Motorola format
Numbers are stored in the Motorola format when higher order bytes are stored first
(in other words, at lower addresses).
MSAC_C1
"Master Slave Acyclic Class 1" - Name for DPC1 in the DP-V1 standard
description.
MSAC_C2
"Master Slave Acyclic Class 2" - Name for DPC2 in the DP-V1 standard
description.
MSB
M
ost
S
ignificant
B
it
MSCY_C1
"Master Slave cyclic class 1" - name of the normal DP master operation in the DP-
V1 standard description.