P1 Panelboards • Quick reference for selection and application
2
Type P1 Panelboards
Selection and Application
3 Easy Steps for Selecting a Siemens Revised P1 Panelboard (Note: Factory assembled panels are configurable in COMPAS)
The Revised P1 Panelboards are now available in both Feed-
thru (FT) and Non-Feed-thru (NFT) variations. There is a
savings of 6” of box height when a NFT version is selected
which eliminates the sub-feed space. The Sub-Feed Space
is where the Feed-thru Lugs, sub-feed breaker or a Surge
Protection Device (SPD) is installed. The interior part number
will end with a “T” for FT panels and will end with an “N” for
NFT panels.
The Revised P1 Panelboards also have Extended Circuit
variations with 54 circuits and 66 circuits available.
Feed-thru (FT) panels are pre-engineered to accept the most
common modifications without increasing box height. The
enclosure size is determined by the number of circuits as shown in
the Main Lug Table P1-5 or the Main Circuit Breaker Table P1-3.
All Revised P1 FT main lug or main breaker panelboards have space
built-in to accept either feed-thru lugs equal to the panel rating
(or) one subfeed circuit breaker up to 250 amperes (or) a surge
suppressor (SPD) without increasing box height. (When ordered
with sub-feed space the interior part # will end with a “T”).
Non-Feed-thru (NFT) panels do not have a sub-feed space and cannot
accept feed-thru lugs (or) sub-feed Breakers (or) SPD/TVSS devices.
(NFT panel interior part # will end in “N”).
Note the following features, all found in the innovative P1
lighting panelboards:
Symmetrical 250A FT Interiors – To change from top to bottom-
feed (or vice-versa), simply invert the interior. The deadfront
labeling is always legible, even on the NFT panels when inverted.
- 400A are not symmetrical, but they are invertable.
First in the Industry Ratings of 125 through 400A main lug and
main breaker. Field convertible from main lug to main breaker
and vice versa – with no increase in enclosure height.
• Field adaptability of feed-thru lugs (or) sub-feed circuit breaker
without increasing enclosure size. (FT panels only)
• Neutral system is field upgradeable to 200% capacity – another
industry first. (also 2/0 neutrals are available as a field install kit)
• Extended circuit panels are now available – up to 66 circuits.
- 18, 30, 42, 54 and 66 circuits for 250A (FT & NFT)
- 26”, 32”, 38”, 44”, 50” and 56” standard Enclosures are used.
Step 1
Determine voltage, system, amperage and
interrupting rating of branch devices, plus
modifications if any.
Example for standard lighting panelboard:
Amperage: 250A
Voltage: 208Y/120V
System: 3Ø4W
Main: Main Lug
Branches: 10K AIR, 42-20/1
Modifications: None
Feed Location: Top
Sub-Feed req’d: Yes (as provision if wanted)
Mounting: Surface
Step 2
Create a catalog number by following the
Panelboard Catalog Numbering System on
- 30, 42 and 54 circuits for 400A (FT & NFT), also 66 circuit NFT
- 56”, 62”, 68” and 74” standard Enclosures are used.
• Suitable for use as service entrance given compliance with NEC.
• Bonding provisions are shipped with each panel.
• 240V and 480Y / 277V versions utilize identical boxes & fronts
Enclosure – Standard Type 1 enclosure is 20” wide x 5.75” deep.
Box Height is determined only by the number of circuits and FT or
NFT selection, not by main lug or main circuit breaker. See charts
P1-3 and P1-5 for box height.
Voltage – 480Y/277 Vac max. (Limited options for 600Y / 347V
Amperage – 400 amp max.
Short Circuit Rating – 200 KAIC max. symmetrical or equal to the
lowest rated device installed unless a series rating is indicated.
Panels with subfeed or feed-thru lugs without a main device,
circuit breaker or fusible unit, are limited to a three-cycle rating.
The three-cycle rating for the P1 panel is limited to 22 KAIC. Note
that the main device may be mounted remote from the panel.
Bussing – The P1 panel meets the majority of the markets
bussing requirements. The standard bussing is temperature rated
aluminum. The rating is per the requirements of UL 67– the
standard for panelboards. All aluminum bussing is tin-plated.
Optional bussing for the P1 panel is temperature rated copper.
The copper bus option for this panel is tin-plated.
Weight – Approximate
Total panelboard weight when filled with a normal quantity of
breakers and accessories is about 3 lbs. (1.36 kg) per inch (54g per
mm) of box height.
Table P1-1 – Box Material Gauge
Width Height (inches) Gauge Steel
20” (250A) 26, 32, 38, 44, 50, 56 #16 (#17 for endwalls)
(400A) 56, 62, 68, 74 #16 (#17 for endwalls)
Table P1-2 – Trim Material Gauge
20” (250A) 26, 32, 38, 44, 50, 56 #14
(400A) 56, 62, 68, 74 #14
page 4. The BL branch breakers were
selected from the branch breaker selection
table 1-6 on page 6.
1-P1C42ML250ATST (“T” indicates FT version)
42-20/1 BL
Note: If Sub-feed space is not needed
the NFT device can be used as below:
1-P1C42ML250ATSN (“N” indicates NFT
version) 42-20/1 BL
Step 3
Select enclosure size by the number
of circuits and FT/NFT as shown in the
panelboard dimension chart (Table P1-3)
on page 5.
1-P1C42ML250ATST
42-20 BL
Box size – 44” high
A unique feature of P1 FT panels is that
they can accommodate either feed-thru
lugs or one subfeed circuit breaker (up to
250A) without any addition to box height.
For our example changing the branch
circuits to 39-20/1 and 1-125/3, we have
the following:
1-P1C42ML250ATST
39-20/1 BL
1-125/3 QJ2
Box size – 44” high
The QJ2 subfeed was selected from Table
P1-7 of subfeed breakers on page 7.
The box height remains the same.