Metasys Network Setup
Metasys Network Setup is described in the Metasys Integrator unit
technical bulletins. This section contains details specific to Siemens
applications.
Mapping to a
CS Object
Table 9: Software Model and CS Object Definition
Application Software Model
(on Tables and
Models CD-ROM)
Display
Attribute
(recommended)
NT Command
Attribute
(recommended)
Model 4300 Power
Meter
SI_4300.DDL AI2 BO1
Model 4700 Power
Meter
SI_4700.DDL AI5 BO1
TRIP III/CPNX
Overcurrent
Device
SI_CPX.DDL AI8 BO2
SAMMS Protective
Relay
SI_SAMMS.DDL BI2 BO1
Access I/O
Addressable
Relay
SI_ACCIO.DDL BI1 BO1
Model 9300 Power
Meter
SI_9300m.DDL AI1 BO2
Model 9500/9600
Power Meter
SI_9500m.DDL AI1 AI1*
* For the NT Command attribute, use the same attribute as the Display attribute.
However, since the points are not commandable, you are not able to command the
attribute. (This must be defined because the NT Command attribute cannot be
null.)