Setup
86
Siemens Building Technologies
Fire Safety & Security Products 08.2007
10.3 SISTORE MX NVS - SISTORE RemoteView - CKA4810 /
CKA4820
Abb. 13 SISTORE MX NVS – SISTORE RemoteViewCKA4810 system
overview
1 CKA4810/20
2 Client PC with
RemoteView
3 MX NVS Server
4 Max. 32 IP cameras
Prerequisite:
The CKA driver is installed (see Section 6.2: Subsequently installing a hardware
driver).
1. Connect the CKA4810/CKA4820 control panel (COM1A port) to the client PC
(COM1/COM2).
2. Configure COM1A on the control panel as an RS232 interface. For more
information please refer to the respective instruction manual for control panel
CKA4810 / CKA4820.
3. Start the SISTORE MX NVS RemoteView application software.
4. Switch to configuration mode.
5. Mark the checkbox CCTV keyboard on the System tab.
6. Click Apply.
Î The setting will be saved.
Î The interface for the control panel is enabled.
Connections
Signal Client PC
SISTORE RemoteView
CKA4810 / CKA4820
9-pin SubD connector
GND 5 5
RXD 3 2
TXD 2 3
Interface configuration CKA4810 / CKA4820
z Protocol: SIMATRIX RS232 or SIEMENS IVM
z Baud rate: 9600
z Parity: none
Zobrazit stránku 85