Commissioning and Diagnostics
6-26
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Channel-Specific Error Messages
Table 6-12 Channel-specific error messages to PROFIBUS standard
Error Type
Error Text Meaning What to Do
00001
B
1
D
Short circuit Short circuit because, for example:
Sensor wiring to P potential short-circuited
Sensor wiring to M potential short-circuited
Output wiring to P potential short-circuited
Output wiring to ground short-circuited
Correct the
process wiring
00010
B
2
D
Undervoltage Supply voltage is below the tolerance range Correct the power
supply
00011
B
3
D
Overvoltage Supply voltage is above the tolerance range Correct the power
supply
00100
B
4
D
Overload The output level is overloaded Correct the
module/actuator
match
00101
B
5
D
Temperature
rise
The output level is overloaded and is too hot Correct the
module/actuator
match
00110
B
6
D
Open circuit Wire break because, for example:
The signal line to a sensor is interrupted
The signal line from an actuator is interrupted
Power cable of the sensor interrupted
Correct the
process wiring.
00111
B
7
D
Upper limit
violation
Value is above the overrange Correct the
module/actuator
match
01000
B
8
D
Lower limit
violation
Value is below the underrange Correct the
module/actuator
match
01001
B
9
D
Error Error, for example, because:
Load voltage at the output
Sensor supply
Hardware error in the module
Contactor is welded or jammed
The switching element has reached the end of
its life
Replace the
module.