2000591-001 Command Summary 69
Command Summary, Continued
This command places a selected port into a hardware diagnostic mode.
The test mode can be used to verify cable continuity and DataNET signal
levels when used in conjunction with an Oscilloscope or other test de-
vice.
The command:
test 1
places port 1 into test mode. The device will generate poll messages on
port 1 every 50 milliseconds. The other port continues to operate nor-
mally. The command:
test off
turns off test mode. Only one port at a time may be in test mode.
This command may be used to disable the user login timeout. Normally,
if a user has not issued a CLI command for five minutes, the device will
automatically shut down the user’s login session. This command may be
used to defeat (and re-enable) this timeout:
timeout off
Disables timeout. The device will not automatically
log out the user, regardless of the time elapsed since
the user last issued a CLI command.
timeout on
Re-enables the five-minute CLI timer.