Mechanical Installation - Metal Sheet Section 2 Installation
16 3BSE056248
The metal sheet shall at least be 2.5 mm thick and at least 180 mm high with
preferably one side bend 90 degrees to increase the stability. The metal sheet shall
be mechanically fastened at least every 500 mm to the cabinet or rack with a
minimum of four screws. The fastening to the cabinet frame shall be performed with
self-tapping screws to get a good grounding connection.
DIN-rail type with height 7.5 mm shall be used. Refer to type NS 35/7.5 according
to standard EN50022.
Figure 3. Mechanical Installation
100
10 0 100 1 00
DIN-ra il 45 0 mm
70
178
266
Al tern at ive an chori ng
of e.g . I/ O cabl es in ap propria te ca ble du ct
Alte rnati ve ancho rin g
of exce ptio nal ca ble s.
Use cable suppor t bar
+ insul ating layer
+ straps
DIN-rail (heigh t 7, 5 mm) mounted with
En d supp ort 2 x 3BSC0224 71R1
tapping screws M6x10
Ensure goo d el ectri cal co nta ct to chassies
For al l b olted join ts
Tapping screws with scratches M6x10