Section 4 Operation S800L I/O Module LED
3BSE056248 51
Marking Color Description
S(Status) Red Fault in the module
(1)
(1) Modules without self test function, for example, DI/DO modules: The S-LED will switch on to red at power up or
restart of the module and switch off after the first successful access to the module. Modules with self test function for
example, AI/AO modules: The S-LED will switch on to red at power up, restart of the module or when the module
goes to Error state. If the module has not gone to Error state it will switch off the S-LED after the first successful
access to the module.
Green Operational state
Module State Status Channel Status
Init Red Off
Not configured Red/Off
(1)
(1) Will be switched off after the first successful access to the module.
Off
Ready Off DI On/Off, DO Off
Operational Green On/Off
OSP Green On/Off
Error Red DI On/Off, DO Off