Siemens Industry, Inc.
Page 7 of 31
BACnet MS/TP Automation Level Network
(ALN)
RS-485, 9600 bps to 115.2 Kbps
BACnet MS/TP Field Level Network (FLN) RS-485, 9600 bps to 76.8 Kbps
on selected models, license required
Human-Machine Interface (HMI) RS-232 compliant, 1200 bps to 115.2 Kbps
USB Device port (for non-smoke control
applications only)
Standard 1.1 and 2.0 USB device port, Type B female connector.
USB Host port
on selected models
Standard 1.1 and 2.0 USB host port, Type A female connector. (for
ancillary smoke control applications only).
Power Requirements 24 Vac ±20% input @ 50/60 Hz
Power Consumption (Maximum)
TC-16: 18 VA @ 24 Vac
TC-24: 20 VA @ 24 Vac
TC-36: 35 VA @
AC Power and Digital Outputs
24 Vac
Communication and all other I/O
NEC Class 1 Power Limited
NEC Class 2
Digital Input
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Does not support counter inputs
Digital Output Class 1 Relay
Analog Output 0 to 10 Vdc
Universal Input (UI) and Universal
Input/Output (U)
Voltage (0-10 Vdc)
Current (4-20 mA)
1K Ni RTD @ 32°F
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Type 2 or Type 3 Thermistor @ 77°F