Appendix C: Device Data Format
60 Siemens Energy & Automation, Inc.
C.4 Device Type: 4720 Power Meter
Real-Time Device Data Stored in PLC (4720 Power Meter)
Real-Time Data Register Location in
PLC Block
Range or Contents
Voltage L-N Phase A 0–1 0...99999999 V
Voltage L-N Phase B 2–3 0...99999999 V
Voltage L-N Phase C 4–5 0...99999999 V
Voltage L-L Phase AB 6–7 0...99999999 V
Voltage L-L Phase BC 8–9 0...99999999 V
Voltage L-L Phase CA 10–11 0...99999999 V
Auxiliary Voltage 12–13 0...999999 V
Current Phase A 14 0...9999 A
Current Phase B 15 0...9999 A
Current Phase C 16 0...9999 A
Current N (I4) 17 0...9999 A
Current Demand Phase A 18 0...9999 A
Current Demand Phase B 19 0...9999 A
Current Demand Phase C 20 0...9999 A
Kilowatts 21–22 -99999999...99999999 kW
Kilowatt Demand 23–24 -99999999...99999999 kW
Kilowatt Hours (total) 25–26 0...1,000,000,000 kWH
Kilowatt Hours (reverse) 27–28 0...1,000,000,000 kWH
Kilovolt-Amperes Reactive 29–30 0...999999 kVAR
Power Factor 31 0...100
PF Lag/Lead 32 0 = Unity, 1 = Lag, 2 = Lead
Frequency 33 0...6000, 0.01 Hz
Current I1 HD - Total 34 0...9999 A
Current I2 HD - Total 35 0...9999 A
Current I3 HD - Total 36 0...9999 A
Voltage Vl HD - Total 37–38 0...99999999 V
Voltage V2 HD - Total 39–40 0...99999999 V
Voltage V3 HD - Total 41–42 0...99999999 V
Sliding Win Kilowatt Demand 43–44 0...99999999 kW
Predicted Slide Win Kilowatt 45–46 0...99999999 kW
Kilovolt-Amperes (Total) 47–48 0...99999999 kVA
Kilovolt-Amperes Reactive Hours
(Total)
49–50 0...99999999 kVARH
Input Status 51 Bits 0–3: Inputs 1–4
Relay Status 52 Bits 0–2: Relays 1–3
Reserved 53–57 Future Expansion
Device Command Data Retrieved From PLC (4720 Power Meter)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to perform Unused for Command 0