Appendix C: Device Data Format
90 Siemens Energy & Automation, Inc.
General Status Word 3:
1
17 Bit Contents
14–15 Not Used
13 Non-dir. ground O/C prot. PICKUP (Valid)
12 Non-dir. ground O/C prot. PICKUP (Status)
11 Non-dir. phase C O/C prot. PICKUP (Valid)
10 Non-dir. phase C O/C prot. PICKUP (Status)
9 Non-dir. phase B O/C prot. PICKUP (Valid)
8 Non-dir. phase B O/C prot. PICKUP (Status)
7 Non-dir. phase A O/C prot. PICKUP (Valid)
6 Non-dir. phase A O/C prot. PICKUP (Status)
5 >51N-BLOCK ground inverse time (Valid)
4 >51N-BLOCK ground inverse time (Status)
3 >50N-BLOCK ground instantaneous (Valid)
2 >50N-BLOCK ground instantaneous (Status)
1 >50NHS-BLOCK ground high-set (Valid)
0 >50NHS-BLOCK ground high-set (Status)
Number of Last Fault 18 0…32767, 0 = no faults
Fault Date/Time (ms) 19 0…59999 (ms )
Fault Date/Time (h/m) 20 High byte: HH (0…23), Low byte: MM (0…59)
Fault Date/Time (m/d) 21 High byte: MM (1…12); Low byte: DD (1…31)
Fault Date/Time (y) 22 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
23 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L1 (I/I
n
)
24 Low word
Interrupted current:
Phase L1 (I/I
n
)
25 High word
Interrupted current:
Phase L2 (I/I
n
)
26 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L2 (I/I
n
)
27 Low word
Interrupted current:
Phase L2 (I/I
n
)
28 High word
Interrupted current:
Phase L3 (I/I
n
)
29 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L3 (I/I
n
)
30 Low word
Interrupted current:
Phase L3 (I/I
n
)
31 High word
Fault in the power system 32 ms since fault (-1 = no fault)
General Trip of Device 33 ms since fault (-1 = no occurrence)
50BF-Breaker Fail TRIP 34 ms since fault (-1 = no occurrence)
Thermal overload protection
trip
35 ms since fault (-1 = no occurrence)
O/C Fault Detection L1 only 36 ms since fault (-1 = no occurrence)
O/C Fault Detection L1-E 37 ms since fault (-1 = no occurrence)
O/C Fault Detection L2 only 38 ms since fault (-1 = no occurrence)
O/C Fault Detection L2-E 39 ms since fault (-1 = no occurrence)
O/C Fault Detection L1-L2 40 ms since fault (-1 = no occurrence)
O/C Fault Detection L1-L2-E 41 ms since fault (-1 = no occurrence)
O/C Fault Detection L3 42 ms since fault (-1 = no occurrence)
O/C Fault Detection L3-E 43 ms since fault (-1 = no occurrence)
Real-Time Device Data Stored in PLC (7SJ511) (Continued)
Function Register Location in
PLC Block
Range or Contents