Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 99
E.13 Device Type: 7SA513
Real-Time Device Data Stored in PLC (7SA513)
Function Register Location in
PLC Block
1
Range or Contents
Current Phase A (I
L1
)0 %
Current Phase B (I
L2
)1 %
Current Phase C (I
L3
)2 %
Voltage L-N Phase A (U
L1
E) 3 %
Voltage L-N Phase B (U
L2
E) 4 %
Voltage L-N Phase C (U
L2
E) 5 %
Watts Three-phase (Pa) 6 %
VAR Three-phase (Pr) 7 %
Frequency (f) 8 %
Voltage L-L Phase AB (U
L12
)9 %
Voltage L-L Phase BC (U
L23
)10 %
Voltage L-L Phase CA (U
L31
)11 %
I
ea
12 mA
I
er
13 mA
General Status Word 1
2
14 Bit Contents
15 Setting group C is active (Valid)
14 Setting group C is active (Status)
13 Setting group B is active (Valid)
12 Setting group B is active (Status)
11 Setting group A is active (Valid)
10 Setting group A is active (Status)
9 Device operative/healthy (Valid)
8 Device operative/healthy (Status)
7 >User defined annunciation 4 (Valid)
6 >User defined annunciation 4 (Status)
5 >User defined annunciation 3 (Valid)
4 >User defined annunciation 3 (Status)
3 >User defined annunciation 2 (Valid)
2 >User defined annunciation 2 (Status)
1 >User defined annunciation 1 (Valid)
0 >User defined annunciation 1 (Status)
General Status Word 2
2
15 Bit Contents
15 >U Line side VT MCB tripped (Valid)
14 >U Line side VT MCB tripped (Status)
13 Failure: Phase sequence supervision (Valid)
12 Failure: Phase sequence supervision (Status)
11 Fuse Failure Monitor Operated (>10s) (Valid)
10 Fuse Failure Monitor Operated (>10s) (Status)
9 Measured value supervision of voltages (Valid)
8 Measured value supervision of voltages (Status)
7 Measured value supervision of currents (Valid)
6 Measured value supervision of currents (Status)
5 Supervision Trip Circuit (Valid)
4 Supervision Trip Circuit (Status)
3 General internal failure of device (Valid)
2 General internal failure of device (Status)
1 Setting group D is active (Valid)
0 Setting group D is active (Status)