Siemens APOGEE™ FLN (P1) Communication Kit
MN04008002E
For more information visit:
www.EatonElectrical.com
3-5
February 2006
LED Indications
The two LED indicators next to the connector show the present status of the Communication
Board (yellow) and the Fieldbus Module (green). See
Figure 3-8
,
Table 3-2
and
Table 3-3
.
Figure 3-8: LED Indications on the Communication Board
Table 3-2: Communication Board Status LED (BS) — YELLOW
Table 3-3: Fieldbus Status LED (FS) — GREEN
LED is: Meaning:
OFF Option board not activated
ON Option board in initialization state waiting for activation command from
the Adjustable Frequency Drive (AFD)
Blinking fast (once/sec) Option board is activated and in RUN state
Option board is ready for external communication
Blinking slow (once/5 secs) Option board is activated and in FAULT state
Internal fault of option board
LED is: Meaning:
OFF Fieldbus module is waiting for parameters from the AFD
No external communication
ON Fieldbus module is activated
Parameters received and module activated
Module is waiting for messages from the bus
Blinking fast (once/sec) Module is activated and receiving messages from the bus
Blinking slow (once/5 secs) Module is in FAULT state
No messages from Master within the watchdog time
Bus broken, cable loose or Master off-line
1
2
3
4
5
X1
Yellow
Yellow
Green
Green
= RS-485 Board Status
= Fieldbus Status