Siemens APOGEE™ FLN (P1) Communication Kit
MN04008002E
For more information visit: www.EatonElectrical.com 5-1
February 2006
Chapter 5 — Siemens FLN (P1) Protocol
Overview
The P1 Protocol provides:
● Direct control of Drive (e.g. Run, Stop, Direction, Speed reference, Fault reset)
● Full access to necessary parameters
● Monitoring of Drive status (e.g. Output frequency, Output current, Fault code)
P1 Point Map
Analog Input (AI) Point Map
Table 5-1: Analog Inputs (AI)
NPT Point Number Description Units
AI 3 FREQ OUTPUT Hz
AI 4 PCT OUTPUT %
AI 5 SPEED rpm
AI 6 CURRENT A
AI 7 TORQUE %
AI 8 POWER %
AI 9 DRIVE TEMP ° F (° C)
AI 10 DRIVE KWH kWh
AI 11 DRIVE MWH MWh
AI 12 RUN TIME Hours
AI 13 DC BUS VOLT V
AI 14 MOTOR VOLT V
AI 43 DRV ACT AO 1 mA
AI 45 DRV ACT AI 1 V
AI 46 DRV ACT AI 2 mA
AI 60 PID FEEDBACK %
AI 65 PID ERROR %
AI 70 DIN STATUS —
AI 71 RO STATUS —
AI 90 LAST FAULT —
AI 91 PREV FAULT —