Upgrading Existing Series 500 Installations
C-15
SIMATIC 545/555/575 System Manual
Table C-1 Analog/Word Output States
RBC Off/Freeze Selection
Analog/Word Module
Zero/Hold Selection
Analog/Word
Output State
Off Zero Zero *
Off Hold Last Value Last Value
Off no selection Last Value
Freeze Zero Last Value
Freeze Hold Last Value Last Value
Freeze no selection Last Value
* See the user manual of your analog/word output module for further details.
Notice that the Freeze option on the RBC overrides the Zero selection on the
analog/word output module; likewise, when Hold Last Value is selected on
the analog/word output module, that selection overrides the Off option on
the RBC jumper.
NOTE: If the RBC watchdog timer is activated (an RBC failure), the state of
the outputs is determined by the output module, with no reference to the
RBCs Off/Freeze switch. Discrete outputs go off (to a value of zero).
Analog/word outputs obey their own Zero/Hold Last Value selection. If no
Zero/Hold Last Value selection is available on the module, the analog/word
outputs hold their last value.
NOTE: The DBC being replaced and previous models of the RBC
automatically set all discrete outputs to Off (0) and froze analog outputs
unless the output module had a ZERO/HOLD LAST VALUE option.