Page 4 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmIntroduction•Material:Liquid or solid; automatically adjusts echo processing with oneentry.
Page 94 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceRemaining Vessel Capacity To perform a volume conversion for the precedi
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 95mmmmmTechnical Reference26 through 32. The mode of communication is established by the configura
Page 96 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceStatus B1 character, $0 to $F (convert to binary, e.g. scan point is in
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 97mmmmmTechnical ReferenceMT-03 Point Not Scanned Field Name DefinitionStart Of Message STX ($02)
Page 98 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmMaintenanceMaintenance The SITRANS LU01 should require no maintenance or cleaning, though g
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 99mmmmmTroubleshootingTroubleshooting Guide Symptom Cause ActionDisplay blank, Transmit Neon not f
Page 100 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTroubleshootingMeasurement Difficulties If a measurement difficulty occurs for greater tha
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 101mmmmmTroubleshootingIf a discernible echo is observed (representative of the material/object su
Page 102 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTroubleshootingIf the preceding remedies have not produced satisfactory results, the false
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 103mmmmmTroubleshootingIncrease the Confidence Threshold (small amounts at a time) while observing
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 5mmmmmSpecificationsSpecifications ElectronicsPower• AC model: 100/115/200/230 V AC ±15%, 50/60 Hz
Page 104 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgramming ChartsProgramming ChartsParameter Altered Values for Indices/Point Numbers# Na
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 105mmmmmProgramming ChartsP116 Bound Alarm DeadbandP129 Relay FailsafemA OutputsP200 mA RangeP201
Page 106 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgramming ChartsP661 Temp fixedP664 Temperature (V)RateP700 Max Fill RateP701 Max Empty
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 107mmmmmProgramming ChartsP802 Submergence TransducerP803 Shot/Pulse ModeP804 Confidence Threshold
*7ml19985BE02*Rev. 2.4www.siemens.com/processautomationSiemens Milltronics Process Instruments Inc.1954Technology Drive, P.O. Box 4225Peterborough, ON
Page 6 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmSpecificationsOutputs• relays: 4 alarm/control relays1 form "C" SPDT contact per r
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 7mmmmmSpecificationsTransducer Compatible Models• STH and Echomax® series • Refer to the associate
Page 8 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmSpecificationsRS-232 Link• Belden 8770, 3 conductor/shielded, 18 AWG (0.75 mm2) or equivalen
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 9mmmmmInstallationInstallation Installation shall only be performed by qualified personnel, and in
Page 10 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationMounting Inspect all cartons and packaging for possible damage during shipment,
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 11mmmmmInstallationInterconnection Before interconnecting system components to the SITRANS LU01 te
Page 12 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationDC ModelWARNINGS:•All field wiring must have insulation suitable for at least 2
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 13mmmmmInstallationOptional SmartLinx ModuleThe standard SITRANS LU01 unit may also be enhanced wi
© Siemens Milltronics Process Instruments Inc. 2008 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that
Page 14 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationSystem DiagramTransducer Note: Maximum system capability. Not all components or
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 15mmmmmInstallationTemperature Sensor Relays mA Outputs109# 1BLKBLKWHT/SHLDWHT/SHLDWHT111213 14TS-
Page 16 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationCommunicationSerialSmartLinxRefer to the appropriate SmartLinx manual for insta
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 17mmmmmInstallationPowerAC Supply Wiring DC Supply Wiring Note: Before making the power connection
Page 18 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationProgrammerCommunications AccessThe hand programmer fits into the docking bay an
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 19mmmmmProgrammingProgramming Operator programmable features are identified by a Point Number and
Page 20 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgrammingKeypad In PROGRAM mode, use the SITRANS LU01 programmer keys to perform the iden
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 21mmmmmProgrammingProgram Mode Entry Upon initial power application, the SITRANS LU01 displays OFF
Page 22 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgrammingParameter Reset Features On initial power up, all parameters are at default valu
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 23mmmmmOperationOperation In RUN mode, the SITRANS LU01 detects material levels and provides contr
iTable of ContentsIntroduction ...
Page 24 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmOperationKeypad In RUN mode, the following programmer keys perform the identified functions
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 25mmmmmOperationSystem Performance Evaluation For initial RUN mode entry (or after any programming
Page 26 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmOperationC. If the SITRANS LU01 provides accurate and repeatable measurements, however alte
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 27mmmmmParametersParameter ReferenceThe SITRANS LU01 is configured through its parameters, and the
Page 28 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersParameter Reset Features On initial power up, all parameters are at original values. I
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 29mmmmmParametersQuick Start (P001 to P007)P001 OperationSets the type of measurement required for
Page 30 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP004 TransducerSpecifies the Siemens Milltronics transducer connected to the unit.P005
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 31mmmmmParametersP006 EmptyEnter distance in units (P005) from the face of the transducer to the p
Page 32 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersApplication ParametersVolume (P050 to P055) Use these parameters to enable the SITRAN
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 33mmmmmParametersP051 Maximum Volume For Readings in volumetric units (rather than percent), enter
iiOperation ...
Page 34 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP052 Tank Dimension ADimension A as used in P050 Tank Shape.Enter one of the following
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 35mmmmmParametersEntering a Level Breakpoint1. Go to Parameter P054.2. Press to display the ind
Page 36 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersDisplay and Reading (P060 to P062) These parameters are used to:• Change the number of
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 37mmmmmParametersP062 Offset ReadingAdds the specified value to the level reading, usually to refe
Page 38 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIf the timer expires (before a valid measurement is made), the SITRANS LU01 advances t
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 39mmmmmParametersRelay reactionThe way in which relay programming reacts to the failsafe level dep
Page 40 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersSetpoints are set up in P112 and P113. Each relay is triggered by one or more setpoint
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 41mmmmmParametersP101 High AlarmEnter the High Alarm material level for the index displayed. .P102
Page 42 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersCustom Relays (P111 to P113) P111 Relay Control FunctionSets the control algorithm use
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 43mmmmmParametersTo reset the Relay Function to use Standard Alarms, enter the desired Relay Set U
iiiEcho Processing Displays (Scope Displays, P810) ...86Dolphin Plus Display ...
Page 44 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02Parameters* Values shown are for illustration purposes only. Enter values which apply to your pa
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 45mmmmmParametersP112 Relay ON SetpointSets the process point at which the relay changes from its
Page 46 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersFor IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a dead
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 47mmmmmParametersmA Output (P200 to P219)When an mA Output Parameter is accessed, the mA symbol is
Page 48 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIndependent mA Setpoints (P210 and P211) Use these features to reference the minimum a
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 49mmmmmParametersPreset is determined by mA Function (P200). If P200 = 1 or 3, then the preset is
Page 50 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersmA Output Failsafe (P219) P219 mA Output Failsafe Use for failsafe operation, independ
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 51mmmmmParametersP302 Temperature, Sensor MaximumView the highest temperature encountered, as meas
Page 52 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersTo manually record a profilePress TRANSDUCER to fire the transducer and record the e
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 53mmmmmParametersP334 Auto Record ON SetpointEnter the critical level which, in conjunction with A
Page 54 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersInstallation Records (P340 to P342) P340 Date of ManufactureView the date of manufactu
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 55mmmmmParametersBefore using this feature, verify the following parameters are correct:•Empty (P0
Page 56 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP652 Offset CorrectionThe value altered when an Offset Calibration is performed.Altern
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 57mmmmmParametersTemperature Compensation (P660 to P664)P660 Temp SourceSource of the temperature
Page 58 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIf Temp Source (P660) is set to any value other than Fixed Temp, the value displayed i
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 59mmmmmParametersP702 Filling IndicatorThe fill rate required to activate the LCD Filling indicato
Page 60 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP705 Rate Update TimeThe time period (in seconds) over which the material level rate o
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 61mmmmmParametersP711 Echo LockUse this feature to select the measurement verification process.If
Page 62 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersExample:Setting• P711 = 2, material agitator• P712 = 5:2Result• a new reading will not
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 63mmmmmParametersThis feature may only be used to adjust the delay before the next point is scanne
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 1mmmmmIntroductionIntroduction SITRANS LU01 The SITRANS LU01 is an ultrasonic long-range level mon
Page 64 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP731 Auxiliary Reading KeyEnter the Parameter Number whose value is to be displayed in
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 65mmmmmParametersPeripheral Communication Support Parameters (P740 to P749)P740 Peripheral Communi
Page 66 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersCommunications (P772) The SITRANS LU01 communication ports are configured by a series
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 67mmmmmParametersP791 Bus ErrorIndicates if an error condition is occuring on the bus.P792 Bus Err
Page 68 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersUse this feature if the surface is reported to be near the transducer face but is in f
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 69mmmmmParametersIncreases SITRANS LU01 response when the monitored surface is close to the transd
Page 70 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP806 Echo StrengthDisplays the strength (in dB above 1 μV rms) of the echo which was s
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 71mmmmmParametersP810 Scope DisplaysCaptures echo profiles for display on an oscilloscope. Use thi
Page 72 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP816 Echo Time RawThe time (in ms) from the transmit pulse to the processed echo. Prof
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 73mmmmmParametersP819 Profile Pointer AmplitudeThe amplitude (in dB above 1 μV) of the Echo Profil
Page 2 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmIntroductionThe distance calculation can be converted to space, material level, material vol
Page 74 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP821 Spike FilterDampens spikes in the echo profile to reduce false readings.Use P821
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 75mmmmmParametersUse this feature, when monitoring solids (P002 = 2), if the reported level fluctu
Page 76 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersSelect the TVT type which gives the highest confidence (P805) under all level conditio
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 77mmmmmParameters6. Press ARROWS to change the bias value of the breakpoint, –50 to 50.7. Pres
Page 78 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersAdvanced Shot Adjustment (P840 to P852) P840 Short Shot NumberThe number of short shot
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 79mmmmmParametersP843 Long Shot FrequencyAdjust the long shot transmit pulse frequency (in kHz).Th
Page 80 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP851 Short Shot FloorEnter the minimum echo strength (in dB above 1 μV rms) derived fr
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 81mmmmmParametersP902 WatchdogPress ENTER to put the CPU into an infinite loop to test the watch
Page 82 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP907 Programmer Interface Press ENTER to activate the programmer interface (two way i
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 83mmmmmParametersMeasurement (P920 to P927)Use these parameters to verify programmng, when perform
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 3mmmmmIntroduction• SmartLinx provides protocol specific hardware and software for interface with
Page 84 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP924 Volume Measurement The calculated vessel capacity in Max Volume (P051) or % of M
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 85mmmmmTechnical ReferenceTechnical Reference Transmit Pulse The SITRANS LU01 transmit pulse consi
Page 86 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceEcho Processing Displays (Scope Displays, P810) Dolphin Plus DisplayDist
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 87mmmmmTechnical ReferenceVariable air temperature is automatically compensated when a Siemens Mil
Page 88 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceThis volume calculation creates a piece-wise linear approximation of the
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 89mmmmmTechnical ReferenceThe Process Speed setting automatically adjusts various parameters affec
Page 90 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceExample 1 - Level Measurement Material Level This is the most common app
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 91mmmmmTechnical ReferenceParameter Settings for Point # 1With process control equipment disabled,
Page 92 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceWhen the dust settles (and the echo is regained) the reported level adva
7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 93mmmmmTechnical ReferenceParameter Settings for Point # 1 Parameter Settings for Ma Output #1 Par