Strany 1 - Instruction Manual May 2008

Instruction Manual May 2008LU01sitrans

Strany 2 - Weighing Systems

Page 4 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmIntroduction•Material:Liquid or solid; automatically adjusts echo processing with oneentry.

Strany 3 - Table of Contents

Page 94 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceRemaining Vessel Capacity To perform a volume conversion for the precedi

Strany 4

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 95mmmmmTechnical Reference26 through 32. The mode of communication is established by the configura

Strany 5

Page 96 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceStatus B1 character, $0 to $F (convert to binary, e.g. scan point is in

Strany 6

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 97mmmmmTechnical ReferenceMT-03 Point Not Scanned Field Name DefinitionStart Of Message STX ($02)

Strany 7 - Introduction

Page 98 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmMaintenanceMaintenance The SITRANS LU01 should require no maintenance or cleaning, though g

Strany 8

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 99mmmmmTroubleshootingTroubleshooting Guide Symptom Cause ActionDisplay blank, Transmit Neon not f

Strany 9 - SITRANS LU01 Features

Page 100 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTroubleshootingMeasurement Difficulties If a measurement difficulty occurs for greater tha

Strany 10 - Response:

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 101mmmmmTroubleshootingIf a discernible echo is observed (representative of the material/object su

Strany 11 - Specifications

Page 102 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTroubleshootingIf the preceding remedies have not produced satisfactory results, the false

Strany 12 - Programmer

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 103mmmmmTroubleshootingIncrease the Confidence Threshold (small amounts at a time) while observing

Strany 13 - Options

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 5mmmmmSpecificationsSpecifications ElectronicsPower• AC model: 100/115/200/230 V AC ±15%, 50/60 Hz

Strany 14 - Safety marking symbols

Page 104 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgramming ChartsProgramming ChartsParameter Altered Values for Indices/Point Numbers# Na

Strany 15 - Recommended

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 105mmmmmProgramming ChartsP116 Bound Alarm DeadbandP129 Relay FailsafemA OutputsP200 mA RangeP201

Strany 16 - Mounting

Page 106 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgramming ChartsP661 Temp fixedP664 Temperature (V)RateP700 Max Fill RateP701 Max Empty

Strany 17 - Interconnection

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 107mmmmmProgramming ChartsP802 Submergence TransducerP803 Shot/Pulse ModeP804 Confidence Threshold

Strany 18 - WARNINGS:

*7ml19985BE02*Rev. 2.4www.siemens.com/processautomationSiemens Milltronics Process Instruments Inc.1954Technology Drive, P.O. Box 4225Peterborough, ON

Strany 19 - Optional SmartLinx Module

Page 6 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmSpecificationsOutputs• relays: 4 alarm/control relays1 form "C" SPDT contact per r

Strany 20

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 7mmmmmSpecificationsTransducer Compatible Models• STH and Echomax® series • Refer to the associate

Strany 21 - Temperature Sensor

Page 8 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmSpecificationsRS-232 Link• Belden 8770, 3 conductor/shielded, 18 AWG (0.75 mm2) or equivalen

Strany 22 - Level System Synchronization

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 9mmmmmInstallationInstallation Installation shall only be performed by qualified personnel, and in

Strany 23 - DC Supply Wiring

Page 10 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationMounting Inspect all cartons and packaging for possible damage during shipment,

Strany 24 - Communications Access

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 11mmmmmInstallationInterconnection Before interconnecting system components to the SITRANS LU01 te

Strany 25 - Programming

Page 12 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationDC ModelWARNINGS:•All field wiring must have insulation suitable for at least 2

Strany 26 - Description

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 13mmmmmInstallationOptional SmartLinx ModuleThe standard SITRANS LU01 unit may also be enhanced wi

Strany 27 - Changing Parameters

© Siemens Milltronics Process Instruments Inc. 2008 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that

Strany 28 - Programming Security

Page 14 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationSystem DiagramTransducer Note: Maximum system capability. Not all components or

Strany 29 - Operation

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 15mmmmmInstallationTemperature Sensor Relays mA Outputs109# 1BLKBLKWHT/SHLDWHT/SHLDWHT111213 14TS-

Strany 30 - Key Description

Page 16 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationCommunicationSerialSmartLinxRefer to the appropriate SmartLinx manual for insta

Strany 31 - Performance Test Results

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 17mmmmmInstallationPowerAC Supply Wiring DC Supply Wiring Note: Before making the power connection

Strany 32

Page 18 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmInstallationProgrammerCommunications AccessThe hand programmer fits into the docking bay an

Strany 33 - Helpful Hints

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 19mmmmmProgrammingProgramming Operator programmable features are identified by a Point Number and

Strany 34 - P000 Lock

Page 20 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgrammingKeypad In PROGRAM mode, use the SITRANS LU01 programmer keys to perform the iden

Strany 35 - Quick Start (P001 to P007)

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 21mmmmmProgrammingProgram Mode Entry Upon initial power application, the SITRANS LU01 displays OFF

Strany 36 - P005 Units

Page 22 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmProgrammingParameter Reset Features On initial power up, all parameters are at default valu

Strany 37 - P007 Span

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 23mmmmmOperationOperation In RUN mode, the SITRANS LU01 detects material levels and provides contr

Strany 38 - Maximum Volume (P051)

iTable of ContentsIntroduction ...

Strany 39 - P051 Maximum Volume

Page 24 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmOperationKeypad In RUN mode, the following programmer keys perform the identified functions

Strany 40 - Universal Volume Calculation

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 25mmmmmOperationSystem Performance Evaluation For initial RUN mode entry (or after any programming

Strany 41 - Entering a Volume Breakpoint

Page 26 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmOperationC. If the SITRANS LU01 provides accurate and repeatable measurements, however alte

Strany 42 - P061 Convert Reading

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 27mmmmmParametersParameter ReferenceThe SITRANS LU01 is configured through its parameters, and the

Strany 43 - P070 Failsafe Timer

Page 28 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersParameter Reset Features On initial power up, all parameters are at original values. I

Strany 44 - P071 Failsafe Material Level

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 29mmmmmParametersQuick Start (P001 to P007)P001 OperationSets the type of measurement required for

Strany 45 - P072 Failsafe Level Advance

Page 30 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP004 TransducerSpecifies the Siemens Milltronics transducer connected to the unit.P005

Strany 46 - P100 Preset Applications

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 31mmmmmParametersP006 EmptyEnter distance in units (P005) from the face of the transducer to the p

Strany 47 - P104 Low Low Alarm

Page 32 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersApplication ParametersVolume (P050 to P055) Use these parameters to enable the SITRAN

Strany 48 - Custom Relays (P111 to P113)

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 33mmmmmParametersP051 Maximum Volume For Readings in volumetric units (rather than percent), enter

Strany 50 - ON OFF Status Alarm Relay

Page 34 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP052 Tank Dimension ADimension A as used in P050 Tank Shape.Enter one of the following

Strany 51 - P116 Dead Band

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 35mmmmmParametersEntering a Level Breakpoint1. Go to Parameter P054.2. Press to display the ind

Strany 52 - P129 Relay Failsafe

Page 36 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersDisplay and Reading (P060 to P062) These parameters are used to:• Change the number of

Strany 53 - P201 mA Output Function

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 37mmmmmParametersP062 Offset ReadingAdds the specified value to the level reading, usually to refe

Strany 54 - P212 mA Output Min Limit

Page 38 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIf the timer expires (before a valid measurement is made), the SITRANS LU01 advances t

Strany 55 - P215 20 mA Output Trim

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 39mmmmmParametersRelay reactionThe way in which relay programming reacts to the failsafe level dep

Strany 56 - P219 mA Output Failsafe

Page 40 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersSetpoints are set up in P112 and P113. Each relay is triggered by one or more setpoint

Strany 57 - P330 Profile Record

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 41mmmmmParametersP101 High AlarmEnter the High Alarm material level for the index displayed. .P102

Strany 58 - P333 Auto Record Interval

Page 42 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersCustom Relays (P111 to P113) P111 Relay Control FunctionSets the control algorithm use

Strany 59 - P337 Auto Record LOE Time

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 43mmmmmParametersTo reset the Relay Function to use Standard Alarms, enter the desired Relay Set U

Strany 60 - P650 Offset Calibration

iiiEcho Processing Displays (Scope Displays, P810) ...86Dolphin Plus Display ...

Strany 61 - • P654 Velocity at 20°C

Page 44 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02Parameters* Values shown are for illustration purposes only. Enter values which apply to your pa

Strany 62 - P654 Velocity at 20°C

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 45mmmmmParametersP112 Relay ON SetpointSets the process point at which the relay changes from its

Strany 63 - P664 Temperature

Page 46 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersFor IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a dead

Strany 64 - Rate (P700 to P707)

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 47mmmmmParametersmA Output (P200 to P219)When an mA Output Parameter is accessed, the mA symbol is

Strany 65 - P704 Rate Filter

Page 48 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIndependent mA Setpoints (P210 and P211) Use these features to reference the minimum a

Strany 66 - P710 Fuzz Filter

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 49mmmmmParametersPreset is determined by mA Function (P200). If P200 = 1 or 3, then the preset is

Strany 67 - P712 Echo Lock Sampling

Page 50 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersmA Output Failsafe (P219) P219 mA Output Failsafe Use for failsafe operation, independ

Strany 68 - P727 Scan Delay

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 51mmmmmParametersP302 Temperature, Sensor MaximumView the highest temperature encountered, as meas

Strany 69 - Display (P730 to P733)

Page 52 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersTo manually record a profilePress TRANSDUCER to fire the transducer and record the e

Strany 70 - P733 Scroll Access

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 53mmmmmParametersP334 Auto Record ON SetpointEnter the critical level which, in conjunction with A

Strany 72 - P790 Hardware Error

Page 54 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersInstallation Records (P340 to P342) P340 Date of ManufactureView the date of manufactu

Strany 73 - P800 Near Blanking

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 55mmmmmParametersBefore using this feature, verify the following parameters are correct:•Empty (P0

Strany 74 - P803 Shot / Pulse Mode

Page 56 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP652 Offset CorrectionThe value altered when an Offset Calibration is performed.Altern

Strany 75 - P805 Echo Confidence

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 57mmmmmParametersTemperature Compensation (P660 to P664)P660 Temp SourceSource of the temperature

Strany 76 - P807 Noise

Page 58 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersIf Temp Source (P660) is set to any value other than Fixed Temp, the value displayed i

Strany 77 - P810 Scope Displays

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 59mmmmmParametersP702 Filling IndicatorThe fill rate required to activate the LCD Filling indicato

Strany 78 - P818 Profile Pointer Distance

Page 60 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP705 Rate Update TimeThe time period (in seconds) over which the material level rate o

Strany 79 - P820 Algorithm

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 61mmmmmParametersP711 Echo LockUse this feature to select the measurement verification process.If

Strany 80 - P823 Reform Echo

Page 62 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersExample:Setting• P711 = 2, material agitator• P712 = 5:2Result• a new reading will not

Strany 81 - Selects the TVT Curve used

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 63mmmmmParametersThis feature may only be used to adjust the delay before the next point is scanne

Strany 82 - P832 TVT Shaper Adjust

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 1mmmmmIntroductionIntroduction SITRANS LU01 The SITRANS LU01 is an ultrasonic long-range level mon

Strany 83 - P835 TVT Slope Min

Page 64 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP731 Auxiliary Reading KeyEnter the Parameter Number whose value is to be displayed in

Strany 84 - P842 Short Shot Frequency

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 65mmmmmParametersPeripheral Communication Support Parameters (P740 to P749)P740 Peripheral Communi

Strany 85 - P850 Short Shot Bias

Page 66 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersCommunications (P772) The SITRANS LU01 communication ports are configured by a series

Strany 86 - Test (P90 0 to P913)

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 67mmmmmParametersP791 Bus ErrorIndicates if an error condition is occuring on the bus.P792 Bus Err

Strany 87 - P906 Communications

Page 68 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersUse this feature if the surface is reported to be near the transducer face but is in f

Strany 88 - P913 Sensor Temperature

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 69mmmmmParametersIncreases SITRANS LU01 response when the monitored surface is close to the transd

Strany 89 - Measurement (P920 to P927)

Page 70 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP806 Echo StrengthDisplays the strength (in dB above 1 μV rms) of the echo which was s

Strany 90 - Master Reset (P999)

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 71mmmmmParametersP810 Scope DisplaysCaptures echo profiles for display on an oscilloscope. Use thi

Strany 91 - Technical Reference

Page 72 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP816 Echo Time RawThe time (in ms) from the transmit pulse to the processed echo. Prof

Strany 92 - Dolphin Plus Display

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 73mmmmmParametersP819 Profile Pointer AmplitudeThe amplitude (in dB above 1 μV) of the Echo Profil

Strany 93 - Universal, Linear (P050 = 9)

Page 2 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmIntroductionThe distance calculation can be converted to space, material level, material vol

Strany 94 - Universal, Curved (P050 = 10)

Page 74 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP821 Spike FilterDampens spikes in the echo profile to reduce false readings.Use P821

Strany 95 - Application Examples

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 75mmmmmParametersUse this feature, when monitoring solids (P002 = 2), if the reported level fluctu

Strany 96 - Material Level

Page 76 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersSelect the TVT type which gives the highest confidence (P805) under all level conditio

Strany 97

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 77mmmmmParameters6. Press ARROWS to change the bias value of the breakpoint, –50 to 50.7. Pres

Strany 98 - Material Volume

Page 78 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersAdvanced Shot Adjustment (P840 to P852) P840 Short Shot NumberThe number of short shot

Strany 99

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 79mmmmmParametersP843 Long Shot FrequencyAdjust the long shot transmit pulse frequency (in kHz).Th

Strany 100 - Application Assistance

Page 80 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP851 Short Shot FloorEnter the minimum echo strength (in dB above 1 μV rms) derived fr

Strany 101 - MT-00 Measurement Message

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 81mmmmmParametersP902 WatchdogPress ENTER to put the CPU into an infinite loop to test the watch

Strany 102 - MT-01 Hold Message

Page 82 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP907 Programmer Interface Press ENTER to activate the programmer interface (two way i

Strany 103 - MT-03 Point Not Scanned

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 83mmmmmParametersMeasurement (P920 to P927)Use these parameters to verify programmng, when perform

Strany 104 - Maintenance

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 3mmmmmIntroduction• SmartLinx provides protocol specific hardware and software for interface with

Strany 105 - Troubleshooting Guide

Page 84 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02ParametersP924 Volume Measurement The calculated vessel capacity in Max Volume (P051) or % of M

Strany 106 - Flashing LOE Display

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 85mmmmmTechnical ReferenceTechnical Reference Transmit Pulse The SITRANS LU01 transmit pulse consi

Strany 107 - Fixed Reading

Page 86 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceEcho Processing Displays (Scope Displays, P810) Dolphin Plus DisplayDist

Strany 108 - Wrong Reading

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 87mmmmmTechnical ReferenceVariable air temperature is automatically compensated when a Siemens Mil

Strany 109 - Troubleshooting

Page 88 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceThis volume calculation creates a piece-wise linear approximation of the

Strany 110 - Programming Charts

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 89mmmmmTechnical ReferenceThe Process Speed setting automatically adjusts various parameters affec

Strany 111 - # Name 1 2 3

Page 90 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceExample 1 - Level Measurement Material Level This is the most common app

Strany 112

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 91mmmmmTechnical ReferenceParameter Settings for Point # 1With process control equipment disabled,

Strany 113

Page 92 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02mmmmmTechnical ReferenceWhen the dust settles (and the echo is regained) the reported level adva

Strany 114 - *7ml19985BE02*

7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 93mmmmmTechnical ReferenceParameter Settings for Point # 1 Parameter Settings for Ma Output #1 Par