7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 53
mmmmm
Parameters
P334 Auto Record ON Setpoint
Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the
boundaries for Auto Profile Records to be saved.
P335 Auto Record OFF Setpoint
Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the
boundaries for Auto Profile Records to be saved.
P336 Auto Record Filling / Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
P337 Auto Record LOE Time
Limits Auto Profile Records from being saved unless extended LOE occurs.
If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.
Values Range: -999 to 9999
Related
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Values Range: -999 to 9999
Related
P334 Auto Record ON Setpoint
P336 Auto Record Filling / Emptying
P337 Auto Record LOE Time
Values
0 * Auto Profile Record on filling or emptying
1 Auto Profile Record on filling only
2 Auto Profile Record on emptying only
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P337 Auto Record LOE Time
P702 Filling Indicator
P703 Emptying Indicator
Values
Range: 0.0 to 9999 (seconds)
Preset: 0.0
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying