UMSITRPDS3-1 On-Line Operation
November 2010
6-5
6.2 LOCAL OPERATION WITH THE MAGNETIC PUSHBUTTONS
The transmitter can be configured locally using the magnetic pushbuttons, shown below. Table 6-2 shows
the operating modes and configuration parameters accessed by pressing the M pushbutton. These
configuration parameters are also available using the HART Communicator.
Note
A selected mode will time out after about 2 minutes of pushbutton inactivity and
the displayed parameter value will be stored.
A polling address of zero (0) must be stored for the magnetic pushbuttons to
function. The magnetic pushbuttons will be disabled if a polling address of 1-15
has been stored, as indicated by a C in the lower left quadrant of the display.