Zobrazit stránku 44
Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 45/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
!
WARNING
The time to be set at parameter PT of the FB F_TON depends on the
application. Generally, this time should be as small as possible. For
times larger than 1 sec additional safety measures should be
considered.
Network 6:
For a set #ERR_SW_TIME bit, the bits 0, 1 and 2 of the cyclic output data
are reset. The bits determine which detection zone is active. Resetting
these bits will cause the laser scanner SIMATIC FS600 to reset the OSSD
bit. In the safety functional example, resetting the OSSD bit causes the
indicator light to be switched off (see FB 3, network 1 and 2).
FC REINTEGRATION (FC3)
In the FC3 a re-integration is implemented for the following components:
Laser scanner SIMATIC FS600 (network 1).
F-DO (network 2).
F-DI (network 3).
The memory bit #REINT is prepared for the F-DO. The F-DO is
reintegrated with a positive edge at the memory bit #REINT.
!
WARNING
In this safety functional example, passivated components are re-
integrated automatically. Use the automatic re-integration for your
application only if it will not cause any hazards.
A passivation is indicated by an illuminated LED “SF” on the F module. The
reintegration of an F module may take about one minute.