Series commissioning and operation
8.1 Transfer of the frequency converter parameter assignment
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
129
8.1.4 Parameter transfer with PC (STARTER)
Upload from frequency converter to the PC
Parameters are uploaded from the frequency converter's RAM to a project file on a PC's
hard disk using STARTER. STARTER can be connected via a fieldbus or directly to the
frequency converter's RS232 interface.
Prerequisites
You must have a converter with a suitable parameter set at your disposal (upload
converter).
STARTER must be installed on the PC used for standard commissioning.
The upload converter's power supply must be connected.
The upload converter is in the "Ready to run" state.
Connect the STARTER PC to the upload frequency converter via RS232 (point-to-point
connection, appropriate connecting cable required) or via fieldbus, press the online button
("Connect to target system") and perform the upload using the button.
Remark
An online connection can only be established between the PC and frequency converter via
fieldbus if the following conditions are met:
The interface module of the ET 200 station is running in DPV1 mode.
There is no CPU between the PC and the frequency converter (also applies to the
Download from PC to the frequency converter
In the case of a manual download, all parameters (with the exception of fail-safe parameters)
will be transferred to the frequency converter.
The parameter download is triggered via STARTER, from the project file in the frequency
converter's RAM.
Note
When making use of this download procedure, you must bear in mind the following important
constraints:
During the download process, the frequency converter will not be able to respond to any
commands.
Once the download procedure is under way, there is no way of stopping it again.
If the data being downloaded are incompatible with the frequency converter, the relevant
parameters in the frequency converter's memory will revert to their default values.
In the event of an unsuccessful download, the frequency converter will not function as it
should.
When parameters are being downloaded from the PC to the frequency converter's
EEPROM, the LEDs will flash. If the frequency converter experiences a fault condition, the
fault is indicated by the LEDs (SF on, RY/RDY off). The download will be carried out
regardless.