Appendix
A.1 Acceptance Log
ET 200pro FC
160 Operating Instructions, 11/2007, A5E01100763B AA
Function test "Safely-Limited Speed" (SLS)
This test comprises the following steps:
Table A-6 "Safely-Limited Speed" function (SLS)
No. Description Status
1. Initial state
Drive is "Ready to Run" (P0010 = 0)
No safety faults and alarms
r9772.4 = r9772.5 = 0 (SLS de-selected and inactive)
2. Operate the drive (if the machine permits it, at a higher speed than the
parameterized safely-limited speed)
3. Check that the expected drive operates
4. Select SLS while issuing the traversing command
5. Check the following:
r9772.4 = 1 (SLS selected)
Drive speed decreases corresponding to the selected ramp time or SLS
mode (if required, use an oscilloscope)
After the parameterized safely-limited speed has been fallen below, the
speed remains below this limit
In SLS mode 1 à correct, must be no fault
In SLS mode 0 à LSTO (safety fault at ramping end)
In SLS mode 2 à LSTO (immediately)
r9772.5 = 1 (SLS active)
6. De-select SLS
7. Check the following:
No safety faults
r9772.4 = r9772.5 = 0 (SLS de-selected and inactive)
8. Check that the expected drive operates if so the following is tested:
The wiring between the control unit and power module is correct
Correct assignment, drive No. – inverter power module – motor
Correct functioning of the hardware
Correct wiring of the shutdown paths
Correct parameterization of the SLS function