Zones
110
Building Technologies
Fire Safety & Security Products
Option Display text Description
-
Up to version 9.07: Spare
3
No Exit Delay
Valid as of version 9.07:
Zone is not an Exit Delay Zone: if this option is turned on the zone will not have any
exit delay and will cause an instant alarm if triggered during the exit delay time. Also
you MUST ensure that if this option is turned on for a zone, that same zone should
not have any entry delay (P144E) programmed. If the zone does have an entry delay
the zone can activate during the exit time thereby starting an entry delay on the same
zone which means the user might not be aware of the pending alarm and leave the
premises. If the zone has no entry delay and the zone is triggered during the exit time
the alarm will then be instant alerting the user that they deviated off the exit route.
According EN 50131-3 the user must have an option to define the zones in the exit
route.
4
Prox Reader
Input
Keypad Zone: if this option is on the Zone will follow the Input at the corresponding
Proximity Reader. If the Proximity Reader is set to Keypad # 1 the input will be either
zone 1 or zone 9, e.g. if P122E 1E (zone #1) had option 4 on then the input at reader
one will operate zone 1. If P122E 9E (zone #9) had option 4 on then the input at
reader one will operate zone 9. Proximity reader 1 can operate zones 1 or 9 through
to proximity reader 8 can operate zones 8 or 16.
5
Radio Device
Zone is a Radio Zone: if this option is on the panel does not scan the hardwired zone
input terminal but instead is looking for a radio zone signal. The correct radio type
should be set at location P127E to ensure that the radio zone works correctly.
6
Stay Mode
Zone is a Stay Mode Zone: if this option is on the zone will be active when Stay Mode
is armed. This feature is normally used for arming just part of the alarm at night time.
7
Bypass able
Zone can be Manually Bypassed: if this option is on the zone can be Manually
Bypassed at the keypad using the
button. A zone must be Bypassed while in the
disarmed state. A bypassed zone will also bypass any tampers associated with that
zone. Once the area with the bypassed zone has been armed then disarmed, the
manual bypass is removed and the zone must be manually bypassed again before
arming if required. If a zone is configured as a 24 Hour zone (P123E Options 3,4 & 5),
they can also Manually Bypassed but in this case the Bypass must be manually
removed to re-instate the zone
8
Auto Bypass able
Zone can be Auto-Bypassed: if this option is on the zone will be Auto-Bypassed if
unsealed at the expiry of the exit delay. If a zone is unsealed at the time of arming
and remains unsealed when the exit delay expires and this option is on for that zone it
will be automatically bypassed by the panel. If the zone seals after that time it will be
re-instated automatically and can then cause an alarm. On disarming of the alarm any
auto-Bypasses are removed