Programming to EN 50131
15
Building Technologies
Fire Safety & Security Products
3 Programming to EN 50131
Necessary programming to EN 50131 installations
The control panel Sintony 60 offers a lot of different features. If the installation must
be according to EN 50131 some of the features and options for users must be
restricted.
To be according EN 50131 requirements the following functions / features must be
programmed as described:
Mute siren
refer to chapter
6.4: Mute siren
This option must be programmed to mute all acoustic devices automatically during
listen-in with the full duplex two way voice board.
According EN 50131-3 if an alarm occurred during Exit Delay the dialer
should reported only after 30sec.
And the Siren shouldn't activate until the Exit delay is expired.
P25E 3E:
Dial Report delay (0-255 Seconds)
refer to chapter
13.3: Dial report delay
If this address is set to 0, there will be no report delay. If it is set to any value other
than 0 then a delay equal to the programmed value will stop the panel from
reporting an instant zone alarm via the dialer until this delay time expires (both
during the exit delay time if option 3 is on at P122E for a zone or when an instant
zone is triggered when fully armed). While the timer is active certain outputs can be
disabled at location P36E option 5. Once the timer has expired it will not start
again, the panel must be disarmed then armed to reset the timer.
According EN 50131-3 if an alarm occurred during Exit Delay the dialer
should reported only after 30sec.
P25E 13E Option 6:
Allow Monitored KP Bus Output Board
refer to chapter
14.3: Miscellaneous user options
Option 6:
Monitored Keypad Bus Output Board: this option performs a similar function to
option 6 at location P25E 10E in that if it is turned on the output status messages
are sent to the keypad bus. The difference with this option is when turned on the
panel is expecting the OUTPUTX4 board connected to the keypad bus to
acknowledge the messages. If the OUTPUTX4 does not acknowledge the output
status messages the panel will show an output board failure. This option should
only be turned on if an OUTPUTX4 board with the latest software is connected to
the keypad bus.
According EN 50131-3 all units connected to the Control Panel should be
monitored.