Additional Information CLV61x Dual Port (PROFINET IO)
8017978 / 2014-11-20 © SICK AG · Germany · All rights reserved · Subject to change without notice 5
The CLV61x Dual Port complies with PROFINET IO Conformance Class B.
The following features are supported:
• Cyclic RT communication.
• Automatic address issue for equipment replacement without engineering tool.
• I&M 0 functionality as well as reading and writing from I&M 1-4
• MediaReduncy support (MRP-Client)
• FAST Ethernet 100 Base TX/FX
• SNMP support
• Neighborhood detection
1.2 Overview of the communication protocol of the CLV61x Dual Port
The CLV61x Dual Port provides two communication protocols. The communication protocol can be set
under "Parameter / Network Interfaces IOs / Profinet":
Operation of the SICK function blocks for PROFIBUS / PROFINET is only possible in Handshake mode /
Confirmed Messaging (CDF600).
CDF600 Handshake mode / Confirmed Messaging (default setting, recommended)
• Data channel compatible with the Byte Handshake Mode of the CDF600 PROFINET,
CDF600 PROFIBUS, CMF400 PROFIBUS, CDM425 and PROFINET on Board.
• Send and receive with max. telegram length of 4000 bytes (with blocking)
• A handshake is required on the PLC side.
• The SICK function blocks can be used for PROFIBUS / PROFINET
• Ctrl bits can be used to trigger or to set I/O's and to monitor.
CDF600 No Handshake mode:
• Data channel compatible with the No Handshake mode of the CDF600 PROFINET,
CDF600 PROFIBUS, CMF400 PROFIBUS, CDM425 and PROFINET on Board.
• The max. telegram length is limited by the size of the input/output range and is max. 123 bytes.
There is no fragmenting / blocking.
• No handshake is required on the PLC side.
• Ctrl bits can be used to trigger or to set I/O's and to monitor.