Digital modules
4.20 Digital output module SM 422; DO 16 x AC 20-120 V/2 A (6ES7422-5EH00-0AB0)
S7-400 Automation System Module Data
172 Reference Manual, Edition 09/2009, A5E00850736-06
Actuator selection data
Output voltage
With "1" signal
L1 (-1.5 Vrms)
Output current
With "1" signal
Nominal value
Permissible range
Permissible inrush current (per group)
2 A
100 mA
to 2 A
Maximum 20 A / 2 cycle
With "0" signal (residual current)
Max. 2.5 mA at 30 V
Max. 4.5 mA at 132 V
Output delay (resistive load)
At "0" to "1" transitions
1 ms
With "1" to "0"
1 AC cycle
Zero transition Non-zero cross outputs
Size of the motor starter Max. size 5 to NEMA
Lamp load Max. 50 W
Wiring two outputs in parallel
For redundant load control
Supported (only outputs of the same group)
For performance increase
Not supported
Triggering a digital input Supported
Switching frequency
With resistive load
Max. 10 Hz
With inductive load in accordance with IEC 947-5-
1, 13 DC
Max. 0.5 Hz
With lamp load
Max. 1 Hz
Short-circuit protection of the output Fuse 8A/125 V 2AG (per output)
Fuse-tripping current
Min. 40 A
Response time
Typ. 33 ms
Replacement fuses
Littelfuse
8 A fuse, fast-blowing
225.008
Changing fuses
WARNING
This can result in injury.
If you change a fuse without removing the front connector of the module, you could be
injured by an electric shock.
Consequently, always remove the front connector before you change the fuse.
Zobrazit stránku 171