Analog modules
5.20 Analog input module SM 431; AI 8 x 14 Bit (6ES7431-1KF10-0AB0)
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
261
Formation of analog values
Measuring principle Integrating
Integration/conversion time/resolution (per channel) (Does not go into the response time)
Programmable
Yes
Noise suppression f1 in Hz
60 / 50
Integration time in ms
16,7 / 20
Basic conversion time in ms
20,1 / 23,5
Additional conversion time for resistance
measurements in ms
40,2 / 47
Additional conversion time for wire break
monitoring in ms
4,3 / 4,3
Additional conversion time for measuring
resistance in ms
5,5 / 5,5
Resolution (including overshoot range)
14/14 bit
Smoothing activated
16/16 bit
Measured value smoothing Parameters can be assigned in 4 stages
Basic execution time of the module, in ms (all
channels enabled)
161 / 188
Noise suppression, error limits
Noise suppression at f = nx (f1 ± 1%)
(f1 = interference frequency) n = 1, 2, ...
Common-mode interference (UCM < 120 Vpp)
> 100 dB
Series-mode interference (peak value of
disturbance < nominal input range)
> 40 dB
Crosstalk between inputs > 70 dB
Operational limit (across temperature range, relative to input range)
Voltage input
± 80 mV
± 250 mV
± 500 mV
± 1 V
± 2.5 V
± 5 V
1 to 5 V
± 10 V
± 0,38 %
± 0,35 %
± 0,35 %
± 0,35 %
± 0,35 %
± 0,35 %
± 0,35 %
± 0,35 %
Current input
0 to 20 mA
± 20 mA
4 to 20 mA
± 0,35 %
± 0,35 %
± 0,35 %