
Analog modules
5.11 Connecting current sensors
S7-400 Automation System Module Data
224 Reference Manual, Edition 09/2009, A5E00850736-06
5.11 Connecting current sensors
Sensor supply voltage
Note
The cables required to connect the analog input module and the sensors are not drawn in
the figures shown below.
In other words, you must continue to read and follow the instructions in the section
"Connecting sensors to analog inputs", which contains general information on connecting
sensors.
The 2-wire sensor is wired to a short-circuit-proof supply voltage at the terminals of the
analog input module. This 2-wire transducer then converts the measured variable into a
current.
Because the 2-wire transducer is supplied by the module, you must not ground the M-
cables.
4-wire transducers require a separate supply voltage U
H
(auxiliary supply).
Connecting 2-wire transducers
1
2 3
4
+24 V
+
-
L+
M+
M-
M+
M-
M
+
-
M
P
P
M
ANA
M +: Measuring line (positive)
M -: Measuring line (negative)
L +: Power supply connection 24 VDC
M
ANA
: Reference potential of the analog measuring circuit
(1) Sensor, for example, pressure gauge
(2) + (3) 2-wire transducer
(4) Connection required for modules with M
ana
Figure 5-8 Connecting 2-wire transducers to an isolated AI
Komentáře k této Příručce