PROFIBUS DP master interface IM 467/IM 467 FO
8.4 Specifications
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
389
8.4 Specifications
8.4.1 Specifications of the IM 467 (6ES7467-5GJ02-0AB0))
Dimensions and weight
Dimensions W x H x D (mm)
Weight
25 x 290 x 210
700 g
PROFIBUS DP
Standard
PROFIBUS DP, EN 50 170
Transmission rate
9.6 Kbps to 12 Mbps, configurable in
steps
Transmission technology
RS 485 via 9-pin sub D socket
Current consumption
Current consumption from the S7-400 bus (24 VDC)
The IM does not consume any current at 24 V, and it only
makes this voltage available at the MPI/DP interface.
Total current consumption of the
components connected to the DP
interfaces, with a maximum of 150
mA
PROFIBUS DP
Operating conditions
Can be used in SIMATIC S7-400, max. 4 IM 467 in
the central rack
IM 467 cannot be used with the CP 443-5
Supply voltage 5 VDC via the backplane bus
Current consumption
From 5 VDC
1.3 A
Addressing range Max. 4 KB for inputs and 4 KB for
outputs
DP master Yes
DPV 1
No
Enable/disable
No
Number of connectable I/O devices (slaves) 96
Number of connections for S7 functions for the programming
device and operator control and monitoring
32 + 1 diagnostic connection
Data volume per slave Max. 244 bytes
Consistency Max. 128 bytes
Configuration software STEP 7
DP slave No