General specifications
1.5 Information on insulation tests, protection class and degree of protection
S7-400 Automation System Module Data
36 Reference Manual, Edition 09/2009, A5E00850736-06
1.5 Information on insulation tests, protection class and degree of
protection
Test voltages
Insulation resistance was demonstrated in routine testing with the following test voltages in
accordance with IEC 61131-2:
Table 1- 11 Test voltages
Circuits with nominal voltage U
e
to other circuits or ground Test voltage
0 V < U
e
≤ 50 V 350 V
50 V < U
e
≤ 100 V 700 V
100 V < U
e
≤ 150 V 1300 V
150 V < U
e
≤ 300 V 2200 V
Protection class
Protection class I in compliance with IEC 61140; this means that a grounding terminal to the
power supply module is required!
Protection against the ingress of foreign matter and water
Degree of protection IP 20 to IEC 60529. In other words, there is protection against contact
with standard probes.
There is no protection against the ingress of water.