Page 188 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P801 Range Extension
Allows the material level to fall below the Empty setting without reporting LOE.
This feature is useful in OCM applications where the Empty level is set to the bottom of
the weir, and above the bottom of the channel, and should be used if the surface
monitored can fall past the Empty (P006) level in normal operation.
The value is added to Empty (P006) and can be greater than the range of the transducer. If
the surface monitored can extend beyond Empty (P006), increase Range Extension (in
Units (P005) or % of Span) such that Empty plus Range Extension is greater than the
transducer face to furthest surface to be monitored distance. This is often the case with
OCM when using weirs and some flumes.
P802 Transducer with Submergence Shield
Used when the transducer is expected to be submerged on occasion.
When a transducer with a submergence shield is submerged, the shield traps an air
pocket that creates a special echo. The HydroRanger 200 recognizes the echo and
advances the reading to the highest level and operates displays and outputs accordingly.
This feature is effective for when power is returned while the transducer is submerged.
Primary Index Global
Values
Range: 0.000 to 9999
Preset: 20% of Span (P007)
Related
P005 Units
P006 Empty
P007 Span
P004 Transducer
Primary Index Global
Values
0*Off
1 Submergence Transducer
Related
P006 Empty
P071 Failsafe Material Level
•Relays