7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 209
mmmmm
Parameters
Master Reset (P999)
This feature resets all parameters to original values.
Use this feature prior to initial programming if arbitrary Parameter Values were used
during a bench test, or after upgrading the software. Following a Master Reset, complete
reprogramming is required.
Performing a Master Reset
1. Access P999 and press CLEAR keys .
2. C.ALL displays until the reset is complete.
CAUTION: be careful when using this feature. All data for all points will be reset. For
convenience, be sure to record the values you want to re-enter.
Primary Index Global
Values Range: 0.000 to 9999