Page 50 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Alarms
With P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112 < P113).
This table shows a high alarm
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by P660.
Loss of Echo (LOE)
Parameter Index Value Description
P111 5 5 Alarm on temperature
P112 5 45 ON setpoint at 45 °C
P113 5 43 OFF setpoint at 43 °C
P110 5 1 Take the temperature reading from
Transducer One
Parameter Index Value Description
P110 5 1 Alarm on LOE for Transducer One
P111 5 6 Alarm on LOE
P070 G 0.5 Trip alarm when 0.5 minutes (30 seconds)
pass without detecting a valid echo.