7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 9
mmmmm
Installation
Cable routed through a conduit:
1. Remove the four mounting screws holding the
motherboard to the enclosure.
2. Be careful not to damage the electronics with static
electricity. Remove the motherboard from the
enclosure by pulling the board straight out.
3. Drill the required cable entry holes. Make sure conduit
holes do not interfere with the lower areas on the
terminal block, circuit board, or SmartLinx card.
4. Attach the conduit to the enclosure using only
approved suitable size hubs for watertight application.
5. Reinstall the motherboard with the mounting screws.
Cable exposed and entering through the cable
glands:
1. Unscrew the glands and attach them loosely to the enclosure.
2. Thread the cables through the glands. Ensure the power cable is kept separated
from the signal cables.
3. Wire the cables to the terminal blocks.
4. Tighten the glands to form a good seal.
HydroRanger 200 Board
Note: Where more holes are required than are supplied in the enclosure, follow the
Cable routed through a conduit
steps.
L2/N L1
TB1
TB3
TB2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
2
1
mA INPUT
SHIELD
SYNC
1
2
4 - 20 mA
OUTP UTS
TS-3
SHIELD
1
2
DISCRETE
INPUTS
RS485
B
A
COM
Battery
RS-232 RJ-11
Connector
Power Supply
Female Connector
for SmartLinx Card
SmartLinx Card
Te r mi na l s
RS-485
Connections
Suitable location for
conduit entrances