SIMATIC S7-400
SIPLUS racks
SIPLUS racks
6/134
Siemens ST 70 · 2013
■
Overview
• The mechanical basic structure of SIPLUS S7-400/S7-400H
• For accommodating the modules, operating voltage supply,
and connection of the modules via a backplane bus
• Several versions for setting up central controllers and
expansion units
• SIPLUS rack material: Aluminum
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific infor-
mation was added.
For further technical documentation on SIPLUS, see:
www.siemens.com/siplus-extreme
■
Ordering data
Order No. Order No.
SIPLUS S7-400 rack
Order No. 6AG1 400-1JA11-7AA0 6AG1 400-1TA11-7AA0 6AG1 400-2JA10-4AA0 6AG1 400-2JA10-7AA0
Order No. based on 6ES7 400-1JA11-0AA0 6ES7 400-1TA11-0AA0 6ES7 400-2JA10-0AA0 6ES7 400-2JA10-0AA0
Ambient temperature range
-25 ... +70 °C -25 ... +70 °C 0...+60 °C -25...+70°C
Conformal coating Coating of the printed circuit boards and the electronic components
Technical data
The technical data of the standard product applies, except for the ambient conditions
Ambient conditions
Relative humidity
100%, condensation/frost permissible. No commissioning if condensation present.
Biologically active substances,
compliance with EN 60721-3-3
Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused
interfaces during operation!
Chemically active substances,
compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must
remain in place over the unused interfaces during operation!
Mechanically active substances,
compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during opera-
tion!
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K
SIPLUS S7-400 rack
(extended temperature range and
medial exposure)
Ambient temperature range
-25 ... +70 °C
UR1 aluminum rack
for central controllers and
expansion units, 18 slots
6AG1 400-1TA11-7AA0
UR2 aluminum rack
for central controllers and
expansion units, 9 slots
6AG1 400-1JA11-7AA0
UR2-H aluminum rack
for central controllers and
expansion units, 9 slots
6AG1 400-2JA10-7AA0
Ambient temperature range
0 ... +60 °C
UR2-H aluminum rack
for central controllers and
expansion units, 9 slots
6AG1 400-2JA10-4AA0