SIMATIC S7-400
Central processing units
SIPLUS high-availability CPUs
SIPLUS CPU 417H
6/49
Siemens ST 70 · 2013
■
Overview
CPU for SIMATIC S7-400H and S7-400F/FH
• Usable in high-availability systems such as the S7-400H
• Usable with F runtime license as F-capable CPU
in S7-400F/FH safety-related systems
• With integral PROFIBUS DP master interface
• Features 2 slots for sync modules
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme specific infor-
mation was added.
■
Technical specifications
6AG1 417-4HT14-4AB0 6AG1 417-4XT05-4AB0 6AG1 417-5HT06-7AB0
Based on 6ES7 417-4HT14-0AB0 6ES7 417-4XT05-0AB0 6ES7 417-5HT06-0AB0
Ambient conditions
Extended ambient conditions
• Relative to ambient temperature-
atmospheric pressure-installation
altitude
Tmin ... Tmax at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa
(+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
Tmin ... Tmax at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa
(+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa
(+3500 m ... +5000 m)
Tmin ... Tmax at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa
(+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa
(+3500 m ... +5000 m).
For "F-Systems" applications max.
+2000 m above sea level permissible
• Relative humidity
- with condensation 100 %; RH incl. condensation/frost
(no commissioning under condensa-
tion conditions)
100 %; RH incl. condensation/frost
(no commissioning under condensa-
tion conditions)
100 %; RH incl. condensation/frost
(no commissioning under condensa-
tion conditions)
• Resistance
- to biologically active substances Yes; Class 3B2 mold, fungus and dry
rot spores (with the exception of
fauna). The supplied connector cov-
ers must remain on the unused inter-
faces during operation!
Yes; Class 3B2 mold, fungus and dry
rot spores (with the exception of
fauna). The supplied connector cov-
ers must remain on the unused inter-
faces during operation!
Yes; Class 3B2 mold, fungus and dry
rot spores (with the exception of
fauna). The supplied connector cov-
ers must remain on the unused inter-
faces during operation!
- to chemically active substances
Yes; Class 3C4 (RH < 75%) incl. salt
spray according to EN 60068-2-52
(degree of severity 3). The supplied
connector covers must remain on the
unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt
spray according to EN 60068-2-52
(degree of severity 3). The supplied
connector covers must remain on the
unused interfaces during operation!
Yes; Class 3C4 incl. salt spray
according to EN 60068-2-52 (degree
of severity 3). The supplied connector
covers must remain on the unused
interfaces during operation!
- to mechanically active substances
Yes; Class 3S4 incl. sand, dust.
The supplied connector covers
must remain on the unused interfaces
during operation!
Yes; Class 3S4 incl. sand, dust.
The supplied connector covers
must remain on the unused interfaces
during operation!
Yes; Class 3S4 incl. sand, dust.
The supplied connector covers
must remain on the unused interfaces
during operation!
Mechanical and climatic conditions
during operation
Climatic conditions in operation
•Temperature
-Min. 0 °C; = Tmin 0 °C; = Tmin -25 °C
-max.
60 °C; = Tmax 60 °C; = Tmax 70 °C; For "F-Systems" applications
max. +60 °C permissible
Kap_06_eng.book Seite 49 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Komentáře k této Příručce