SIMATIC S7-400
Central processing units
Standard CPUs
CPU 416
6/15
Siemens ST 70 · 2013
Technical specifications (continued)
6
Isochronous mode
Isochronous operation (application
synchronized up to terminal)
Yes; For PROFIBUS only Yes; For PROFIBUS only Yes; Via PROFIBUS DP or
PROFINET interface
Communication functions
PG/OP communication Yes Yes Yes
Data record routing
Yes Yes Yes
Global data communication
• supported Yes Yes Yes
S7 basic communication
• supported Yes Yes Yes
S7 communication
• supported Yes Yes Yes
S5-compatible communication
• supported Yes; Via FC AG_SEND and AG_RECV,
max. via 10 CP 443-1 or 443-5
Yes; Via FC AG_SEND and AG_RECV,
max. via 10 CP 443-1 or 443-5
Yes; Via FC AG_SEND and AG_RECV,
max. via 10 CP 443-1 or 443-5
Standard communication (FMS)
• supported Yes; Via CP and loadable FB Yes; Via CP and loadable FB Yes; Via CP and loadable FB
Open IE communication
•TCP/IP Yes; via integrated PROFINET
interface and loadable FBs
- Number of connections, max.
94
• ISO-on-TCP (RFC1006)
Via CP 443-1 and loadable FB Via CP 443-1 and loadable FB Yes; Via integrated PROFINET
interface or CP 443-1 and
loadable FBs
- Number of connections, max.
94
UDP
Yes; via integrated PROFINET
interface and loadable FBs
- Number of connections, max.
94
Web server
• supported No No Yes
Number of connections
•overall 64 64 96
Configuration
programming
• Programming language
-LAD Yes Yes Yes
-FBD
Yes Yes Yes
-STL
Yes Yes Yes
-SCL
Yes Yes Yes
-CFC
Yes Yes Yes
- GRAPH
Yes Yes Yes
-HiGraph®
Yes Yes Yes
Know-how protection
User program protection/password
protection
Yes Yes Yes
• Block encryption
Yes; With S7 block Privacy
Dimensions
Width 25 mm 50 mm 50 mm
Height
290 mm 290 mm 290 mm
Depth 219 mm 219 mm 219 mm
Required slots
1 2 2
Weight
Weight, approx. 0.7 kg 0.9 kg 900 g
6ES7 416-2XN05-0AB0 6ES7 416-3XR05-0AB0 6ES7 416-3ES06-0AB0
CPU 416-2 CPU 416-3 CPU416-3 PN/DP
Kap_06_eng.book Seite 15 Donnerstag, 2. Mai 2013 4:16 16