SIMATIC S7-400
Analog modules
SM 431 analog input module
6/67
Siemens ST 70 · 2013
Technical specifications (continued)
6
Basic error limit
(operational limit at 25 °C)
Voltage, relative to input area +/- 0,25 %;
0.5% at 1 to 5 V;
0.25% at +/-1 V, +/-10 V
+/- 0,6 %;
0.6% at +/-1 V;
0.75% at +/-10 V, 1 to 5 V
+/- 0,7 %;
0.7% at +/-1 V;
0.4% at +/-10 V;
0.5% at 1 to 5 V
+/- 0,15 %;
+/-0.15%(+/-250 mV,
+/-500 mV, +/-1 V, +/-2.5 V,
+/-5 V, 1 to 5 V, +/- 10 V);
+/-0.17% (+/- 80 mV);
Current, relative to input area
+/- 0,25 %;
at +/-20 mA, 4 to 20 mA
+/- 0,7 %;
at +/-20 mA, 4 to 20 mA
+/- 0,7 %;
at +/-20 mA, 4 to 20 mA
+/- 0,15 %; +/-20 mA,
0 to 20 mA, 4 to 20 mA
Impedance, relative to input area
+/- 0,7 %; 0 to 600 ohms +/- 0,8 %; 0 to 500 ohms
(4-conductor measurement,
in range of 600 ohms)
+/- 0,15 %; +/-0.15% at 0 to
48 ohms (4-conductor mea-
surement), 0 to 150 ohms
(4-conductor measure-
ment), 0 to 300 ohms
(4-conductor measure-
ment), 0 to 600 ohms
(4-conductor measure-
ment), 0 to 5000 ohms
(4-conductor measurement,
in range of 6000 ohms);
+/-0.3% at 0 to 300 ohms
(3-conductor measure-
ment), 0 to 600 ohms
(3-conductor measure-
ment), 0 to 5000 ohms
(3-conductor measurement,
in range of 6000 ohms)
Resistance-type thermometer,
relative to input area
+/- 0,3 %
Galvanic isolation
Galvanic isolation analog inputs
Galvanic isolation analog inputs No Yes; internal/external Yes; internal/external Yes; internal/external
between the channels
No No No No
Permissible potential difference
between the inputs (UCM) 2 V DC / 2 Vpp AC 8 V AC 30 V AC 120 V AC
Isolation
Isolation checked with 500 V DC between bus
and local ground
2120 V DC between bus
and analog part; 500 V DC
between bus and local
ground; 707 V DC between
analog part and L+/M;
2120 V DC between analog
part and local ground;
2120 V DC between L+/M
and local ground
2120 V DC between bus
and analog part; 500 V DC
between bus and local
ground; 2120 V DC
between analog part and
local ground
2120 V DC between bus
and L+/M; 2120 V DC
between bus and analog
part; 500 V DC between
bus and local ground;
707 V DC between analog
part and L+/M; 2120 V DC
between analog part and
local ground; 2120 V DC
between L+/M and local
ground
Dimensions
Width 25 mm 25 mm 25 mm 25 mm
Height 290 mm 290 mm 290 mm 290 mm
Depth
210 mm 210 mm 210 mm 210 mm
Required slots 1 1 1 1
Weight
Weight, approx. 500 g 500 g 500 g 500 g
6ES7 431-0HH00-0AB0 6ES7 431-1KF20-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0