UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
5
-
9
5. Press SEL/CONT (F4) to configure the alarm type.
6. Press NEXT OPTN (F2) to choose either HIGH or LOW.
7. Press SEL/CONT (F4) to configure Alarm 2 or SEL/END
(F3) to return to the Function Block Menu.
8. At the SELF CLEARING NAKS screen press NEXT
OPTN (F2) to choose ON or OFF.
9. At the ALARMS OUT OF SERVICE screen press NEXT
OPTN (F2) to choose OFF or ON and SEL/CONT (F4) to
return to the Function Block Menu.
5.1.1.6 Setpoint Track and Hold
Block
This function block can be configured as tracking or non-
tracking. When configured as tracking, the SP will track the PV
when the controller is in manual. If it is configured as non-
tracking the SP will remain at its hold value. On power -up, the
operating value in the function block is initialized to the Power-Up
(PUSP) value.
1. At the SP TRACK & HOLD menu press SELECT (F4) to
configure the TRACKING SETPOINT block. Press NEXT
OPTN (F2) to choose either YES or NO. Press SEL/CONT
(F4) to continue to the PUSP screen.
2. At the PUSP screen Press EDIT (F1) to edit the setpoint.
Press ENTER (F4) to change the setpoint or QUIT (F3) to
exit without changing the setpoint. Press SEL/CONT (F4) to
return to the Function Block Menu.
5.1.1.7 A/M Transfer Block
The A/M Transfer may be configured to power-up in Automatic
or Manual. From the A/M Transfer Menu choose SELECT (F4)
for the POWER-UP MODE screen.
1. Press NEXT OPTN (F2) to choose between AUTOMATIC
AND MANUAL. Press SEL/CONT (F4) for the
AUTOMATIC MODE ONLY screen.
2. Press NEXT OPTN (F2) to choose YES or NO. When
YES is selected the function block will always remain in the
AUTO position. Press SEL/CONT (F4) for the POWER-
UP VALVE screen.
SELF CLEARING NAKS:
ON
LAST
NEXT
SEL/
SEL/
OPTN OPTN CONTEND
ALARMS OUT OF
SERVICE: OFF
LAST
OPTN
NEXT
OPTN
SEL/
END
SEL/
CONT
LAST
OPTN
NEXT
OPTN
SEL/
END
SEL/
CONT
TRACKING SETPOINT:
NO
SEL/
END
SEL/
CONT
PUSP: 55.000 DEG F
0.0000 TO 100.00
EDIT
SEL/
END
SEL/
CONT
LAST
OPTN
NEXT
OPTN
POWER-UP MODE:
AUTOMATIC
SEL/
END
SEL/
CONT
LAST
OPTN
NEXT
OPTN
AUTOMATIC MODE ONLY:
NO