ON-LINE AND OFF-LINE OPERATION UM344-2
September 1995
4. Use PREV and NEXT to select the transmitter type -
Temperature - then press SELECT. The default configur-
ation for a temperature transmitter will be loaded into the
Off-Line Memory of the MXC.
5. The next screen shows the archive number to be edited.
Press either EDIT ARCH to begin editing or END to select
another archive number.
6. Press CONT to continue and select a configuration block for
editing. Refer to Section 5.1.1 to edit configuration
parameters.
Press QUIT to return to the previous screen.
After configuration is complete:
1. Press END in the Function Block menu to access the
following three choices from the adjacent screen.
QUIT - go to the Main Menu and end configuration.
REVIEW - return to the Function Block menu to make any
changes or additions. Refer to Section 5.1.1 as necessary.
SAVE - show the archive number and tagname of the
current configuration and provide the option to save the
configuration either under the current archive number or
under a new number. Go to step 2.
2. Press YES in the Save Archive screen to save the archive
under the current number. Perform one of the two steps
below:
Ÿ If the new configuration will overwrite an existing
archive, the MXC will provide a warning message before
the store operation is performed. Press ENTER to
continue.
Ÿ If the tagname of a new configuration has already been
assigned to an archived configuration, a WARNING
screen appears. Press CONT to move to the TRANS-
MITTER ID block and display the tag selection.
- If the tagname is not to be changed, press either
SEL/END to return to the Save Archive screen or
SEL/CONT to return to the previous screen.
SELECT X-MITTER TYPE
TEMP CONTROLLER
PREV
NEXT
END
SEL-
ECT
ARCHIVE 97 DEFAULT
SELECT A FUNCTION
EDIT
ARCH END
CONFIGURATION
COMPLETE
RE-
QUIT SAVE VIEW
SAVE TO ARCHIVE 97
DEFAULT
NEW
YES ARCH END
ERROR! ARCHIVE TYPE
DOESN'T MATCH THE
TRANSMITTER TYPE
CONT
WARNING: TAG NAME
USED ENTER NEW TAG
NAME.
CONT