Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
131
10.3 Overview of parameters
10.3.1 Overview of parameters 1 to 5
Introduction
Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to
adjust the positioner to the actuator. Normally the parameter setup is sufficient to be able to
operate the positioner on an actuator.
If you want to get to know the positioner in detail, gradually try out the effects of the
remaining parameters by systematic testing
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter Function Parameter values Unit
Type of position actuator
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (part-turn actuator with NCS, inverse
direction of action)
ncSL (linear actuator with NCS)
1.YFCT
ncSLL (linear actuator with NCS and lever)
Nominal angle of rotation of the feedback message
1)
33°
2.YAGL
90°
Degrees
Range of stroke (optional setting)
3)
OFF
5 | 10 | 15 | 20
(Short lever 33°)
25 | 30 | 35
(Short lever 90°)
3.YWAY
2)
40 | 50 | 60 | 70 | 90 | 110 | 130
(Long lever 90°)
mm
4.INITA Initialization (automatic) NOINI | no / ###.# | Strt
5.INITM Initialization (manual) NOINI | no / ###.# | Strt