Alarm, error, and system messages
11.3 Online diagnostics
SIPART PS2 with and without HART communications
188 Operating Instructions, 09/2007, A5E00074631-07
11.3.2 XDIAG parameter
You can use the advance diagnostics parameters to display fault messages in one, two or
three stages. In addition to the fault message output, alarm outputs 1 and 2 are then used.
For this purpose, set the "XDIAG" parameter as described in the following table:
Settings of XDIAG Message due to
OFF Advanced diagnostics not activated
On 1 Fault message output for threshold 3 fault messages (one-stage)
On 2 Fault message output for threshold 3 fault messages and alarm output 2 for threshold 2
fault messages (two-stage)
On 3 Fault message output for threshold 3 fault messages and alarm output 2 for threshold 2
fault messages and alarm output 1 for threshold 1 fault messages (three-stage)
Possible settings of the "XDIAG" parameter
11.3.3 Overview of error codes
Overview of error codes that activate the fault message output
Error
code
Three-
stage
Event Parameter setting Fault message disappears
when
Possible causes
1 No Remaining control
deviation
Always active ... the control deviation
disappears again.
Compressed air failure,
actuator fault, valve fault (e.g.
blockade).
2 No Device not in the
automatic mode
**. FCT
1)
=
nA or = nAB
... the device is switched to
the automatic mode.
The device has been
configured or is in the manual
mode
3 No Binary input BE1
or BE2 active
**. FCT
1)
=
nAB and binary
function BIN1 or
BIN2 on "On"
... the binary input is no
longer active.
The contact connected to the
binary input was active (e.g.
packing gland monitoring,
overpressure, temperature
switch).
4 Yes The limit of stroke
number exceeded
L. STRK≠OFF ... the stroke counter is reset
or the thresholds are
increased
The total path covered by the
actuator exceeds one of the
set thresholds.
5 Yes Limit of changes of
direction exceeded
O. DCHG≠OFF ... the counter for changes of
direction is reset or the
thresholds are increased.
The number of changes of
direction exceeds one of the
set thresholds.
6 Yes Limit of the lower
hard end stop
exceeded
F. ZERO≠OFF
**.YCLS = do or up
do
... the deviation of the end
stop disappears or the device
is re-initialized.
Wear and tear of the valve
seat, deposits or foreign
bodies in the valve seat,
mechanical misalignment,
friction clutch moved.