Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
132 Operating Instructions, 09/2007, A5E00074631-07
1)
Set the transmission ratio selector accordingly.
2)
The parameter only appears for "WAY" and for "ncSLL".
3)
When used the value must correspond with the set range of stroke on the actuator.
Carriers must be scaled to the actuator's stroke value,or if this is not scaled they then must be set to the next
largest scaled value.
10.3.2 Overview of parameters 6 to 51
Introduction
These parameters are used to configure the following additional functions of the positioner:
Target value preparation
Actual value preparation
Binary signal processing
Tight closing function
Boundary value detection
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter Function Parameter values Unit
Current range of setpoint
0 ... 20 mA 0 MA
6.SCUR
4 ... 20 mA 4 MA
Setpoint setup
Rising riSE
7.SDIR
Falling FALL
8.SPRA Setpoint split range start 0.0 ... 100.0
9.SPRE Setpoint split range end 0.0 ... 100.0
10.TSUP Setpoint ramp OPEN Auto / 0 ... 400
11.TSDO Setpoint ramp CLOSED 0 ... 400