SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
173
Alarm, error, and system messages
11
11.1 Representation of system messages in the digital display
11.1.1 System messages before initialization
Remarks about the tables:
nn stands for variable numeric values
Error symbol
/ (Slash): texts to the left and the right of the slash blink alternately
Messages before initialization (first commissioning)
Line Message
Up Down
Meaning / cause Measure
CPUStart X
X
Message after connecting the electrical
auxiliary power supply
Wait
Pnnn.n X Potentiometer voltage of a non-initialized
positioner (P-manual mode) (actual position
value in % of the measuring range)
Check whether the entire actuator travel
can be covered using the "+" and "-"
buttons and "P---" is never displayed
Execute the initialization process
P--- X Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
Switch the transmission ratio selector to
90° especially in case of part-turn
actuators
Adjust the effective lever length of linear
actuators as per the measuring range
NOINI X Positioner is not initialized
Start the initialization process
See also
Digital display (Page 91)