11 Alarms 11.90
11.11 Alarm list ACKNOWLEDGE
6112
MC 5 - command STP
Cause:
Effect:
Explanation:
STP instruction programmed
PLC STOP
PLC STOP after termination of STEP 5 program processing
6113
Illegal MC 5 timer / counter
Cause:
Effect:
Remedy:
STEP 5 timer or counter not available or not enabled via MD. Time with
a constant of 10 ms progr.
PLC STOP.
• Correct program, correct time constant (100 ms, 1 s, 10 s)
• Change PLC MD 6
6114
Function macro
Cause:
Effect:
Remedy:
Error in use of a function block (basic program)
PLC STOP
See Programming Guide, Function Macros
Evaluate ISTACK (error number in ACCU 2)
6115
System commands disabled
Cause:
Effect:
Remedy:
Programmed command LIR, TIR, TNB, TNW
PLC STOP
Set PLC MD 2003 bit 4
6116
MD 0000: Alarm byte No.
Cause:
Effect:
Remedy:
PLC MD 0 set greater than 31
PLC STOP
Correct MD
11–52 © Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02
SINUMERIK 810 GA3/820 GA3 (IA)